MCT-CM
164
10.5 Analog Inputs
The MCT supports up to 14 analog inputs which are used for remote set point inputs. Each of the available
analog inputs can be configured from the ‘Analog Input’ screen.
The left and right navigation buttons at the upper right of the screen allow the user to scroll through each
available input. To make changes to the analog input’s configuration, select the desired input type by pressing
the voltage (Vdc) or current (mA) button to select a 2-10V or a 4-20mA input signal.
NOTE:
If the analog input type is changed from voltage to current or vice versa, power must be cycled to the
MCT controller in order for the input to switch signal types.
Select the desired loop by pressing the ‘Destination’ button to select from the list of available control loops.
Se
lect the desired control loop and press the ‘Return’ button to return to the Analog Input screen. Enter the
desired minimum and maximum values for the loop set point that the input is to represent. The input range is -
32760 to 32760 for a decimal point resolution of zero, -3276.0 to 3276.0 for a decimal point of one, -327.60 to
327.60 for a decimal point of two and -32.760 to 32.760 for a decimal point resolution of three.
The function selection buttons,
None
and
SP
, enable and disable the analog input. This allows the analog input
configuration to be maintained, but disable its operation until it is required. Select ‘None’ to prevent the analog
input from taking set point control over the selected loop. Press the ‘SP’ button to enable the analog input set
point control override.
Once all settings have been made, press the ‘Save’ button to save the changes. If you do not press the ‘Save’
button, all changes will be lost if you leave the screen or navigate to another analog input.
Summary of Contents for MCT-CM
Page 20: ...MCT CM 20...
Page 24: ...MCT CM 24...
Page 45: ...MCT CM 45...
Page 187: ...MCT CM 187...
Page 227: ...MCT CM 227 A 4 Control Module Specifications Main CPU...
Page 228: ...MCT CM 228...
Page 229: ...MCT CM 229...
Page 230: ...MCT CM 230...
Page 231: ...MCT CM 231 Analog I O Card...
Page 232: ...MCT CM 232...
Page 233: ...MCT CM 233 Digital Input Card...
Page 234: ...MCT CM 234...
Page 235: ...MCT CM 235 Digital Output Card...
Page 236: ...MCT CM 236...
Page 237: ...MCT CM 237 Dual Communications Card Barcode and Remote Display Communication Cartridges...
Page 238: ...MCT CM 238 A 5 Power Supply Specifications...
Page 239: ...MCT CM 239...
Page 240: ...MCT CM 240 A 6 Power On Delay Relay Specifications GE1A C10HA110...
Page 241: ...MCT CM 241...