MCT-CM
152
NOTE:
Any changes made to the above settings must be saved in order for them to take effect. When changes
are complete, press the
‘Save’ button to save the new settings in order to use them.
The
Bar Code Test
field allows the operator to test the operation of the barcode scanner. As a bar code is
swiped by the reader, the scanned value will appear in this field. If upon scanning a bar code, no value appears
in this field, check the wiring and communication settings of the barcode scanner to be sure that it is connected
and set up properly.
9.9.1
Barcode Reader Communication Settings
In order for the barcode scanner to communicate properly with the MCT, it must be set with the proper
communication settings. This includes baud rate, data bits, stop bits, parity and start/end of transmission
characters as follows:
Baud rate = 9600 baud
Data bits = 7
Stop bits = 1
Parity = even
Preamble = STX (0x02)
Postamble = ETX (0x03)
The preamble and postamble are the start of transmission and end of transmission characters that must be
used to frame the barcode transmitted to the MCT so that it recognizes the beginning and end of the
transmission. All other terminator, BCC, ACK and/or handshaking characters must be disabled.
9.9.1.1
Setting up the Unitech MS-120-2 Barcode Scanner
The following instructions are provided for the Future Design Controls recommended Unitech MS-120-2
barcode scanner. These instructions do not apply to other makes or models of scanner. Consult the
manufacturer’s manual for other makes or models for information on how to set the proper communications
settings.
NOTE:
The steps below are assuming manufacturer default settings are in place. If the scanner settings are
unknown, restore the scanner to manufacturer defaults by scanning barcode ‘enter group 1’ on page
5 of the MS-
120 Series Programming Manual and then scanning the ‘factory defaults’ barcode at the
bottom of page 5. Scan ‘exit’ to complete the process.
For communication settings see page 11 (RS232 Serial Setting) of the MS-120 Series Programming Manual
Step 1
scan barcode at top of page 11 for ‘enter group 4’
Step 2
scan barcode C2 for parity on page 12 and then scan the barcode for the number 0 on page 11
Step 3
scan barcode C3 for data bit on page 12 and then scan the barcode for number 0 on page 11
Step 4
scan the barcode for ‘exit’ on page 11 to complete RS232 settings
For pre/postamble settings see page 13 (Scanner) of the MS-120 Series Programming Manual
Step 1
scan barcode at top of page 13 for ‘enter group 5’
Summary of Contents for MCT-CM
Page 20: ...MCT CM 20...
Page 24: ...MCT CM 24...
Page 45: ...MCT CM 45...
Page 187: ...MCT CM 187...
Page 227: ...MCT CM 227 A 4 Control Module Specifications Main CPU...
Page 228: ...MCT CM 228...
Page 229: ...MCT CM 229...
Page 230: ...MCT CM 230...
Page 231: ...MCT CM 231 Analog I O Card...
Page 232: ...MCT CM 232...
Page 233: ...MCT CM 233 Digital Input Card...
Page 234: ...MCT CM 234...
Page 235: ...MCT CM 235 Digital Output Card...
Page 236: ...MCT CM 236...
Page 237: ...MCT CM 237 Dual Communications Card Barcode and Remote Display Communication Cartridges...
Page 238: ...MCT CM 238 A 5 Power Supply Specifications...
Page 239: ...MCT CM 239...
Page 240: ...MCT CM 240 A 6 Power On Delay Relay Specifications GE1A C10HA110...
Page 241: ...MCT CM 241...