MCT-CM
33
3.4.1.2
US2000B Communication Module to Loop Controls
Communications Wiring Example (FDC-9300 controller shown)
3.4.2
Assigning the Proper Communications Settings
The MCT-CM can support up to ten C-Series R22 controls or up to ten FDC 300 Series controls depending
upon the firmware version installed in the CM. Each loop control must have its own communication address.
The allowable address range is 1
– 10 corresponding to Loop Input #1 – 10 in the MCT Configurator.
Communication addresses must be assigned to all controls on the communications link beginning with 1, up to
the total number of controls.
As control loops are enabled in the MCT Configurator, the MCT will automatically use the Loop Input # as the
corresponding controller address. If more than one loop control has the same address, or a loop input is
enabled but a control is not assigned to that address, the MCT will report a communications alarm for that loop
input when the runtime application is started.
NOTE:
The order of the loop controls on the communication link is not important. The communications
address for a control can be assigned regardless of its position on the link.
In addition to the communications address, the baud rate, data bits, stop bits and parity settings must also be
set to match the control module of the MCT. The MCT control module uses the factory default communication
rate of 9600 baud, 8 data bits and 1 stop bit; however, the parity of the C-Series R22 or FDC 300 Series control
must be changed from the factory default of “even” to “none”.
Summary of Contents for MCT-CM
Page 20: ...MCT CM 20...
Page 24: ...MCT CM 24...
Page 45: ...MCT CM 45...
Page 187: ...MCT CM 187...
Page 227: ...MCT CM 227 A 4 Control Module Specifications Main CPU...
Page 228: ...MCT CM 228...
Page 229: ...MCT CM 229...
Page 230: ...MCT CM 230...
Page 231: ...MCT CM 231 Analog I O Card...
Page 232: ...MCT CM 232...
Page 233: ...MCT CM 233 Digital Input Card...
Page 234: ...MCT CM 234...
Page 235: ...MCT CM 235 Digital Output Card...
Page 236: ...MCT CM 236...
Page 237: ...MCT CM 237 Dual Communications Card Barcode and Remote Display Communication Cartridges...
Page 238: ...MCT CM 238 A 5 Power Supply Specifications...
Page 239: ...MCT CM 239...
Page 240: ...MCT CM 240 A 6 Power On Delay Relay Specifications GE1A C10HA110...
Page 241: ...MCT CM 241...