MCT-CM
108
6.3 Monitoring Automated Ramp/Soak Program Operation
The program Status view provides all information regarding the operation of the current program.
Status
indicates the current operating mode of the program, i.e., active, hold, ramp, steady, waiting, etc.
Start
indicates the date and time at which the program was started.
End
is the calculated stop date and time for the program.
Step
indicates the step number currently being executed.
Time
is the time remaining in the current step.
Wait
indicates the input(s) being monitored if a wait for condition is present.
Wait SP
shows the set point or digital input number for the wait for condition if active.
Jump
indicates the step number that program will jump to at the completion of the current step.
Cycles
indicates the number of jumps remaining for the step (if any).
The
loop set points
for the current step can be viewed at the top of the screen by pressing the left and right
scroll buttons to cycle through each loop configured in the system. Note that the set points shown here are the
target set points, not the actual set points the loops are controlling to. To view the actual control set point, see
the Single, Dual or Overview screens.
IMPORTANT: If the set point does not match the set point programmed for the step, the set point may exceed
the configured set point range for the loop. If a step set point exceeds a limit, it will be coerced
to the lower or upper limit that it exceeds. This is done automatically without altering the original
program.
The set point limits are those defined in the MCT configuration for the loop, not those on the
set point Limits screen under the device setup menu. It is not possible to enter set points for a
program that exceed the configured set point limits; however, if the program was imported from
another MCT system with set point limits exceeding those of the current system, this can occur.
Summary of Contents for MCT-CM
Page 20: ...MCT CM 20...
Page 24: ...MCT CM 24...
Page 45: ...MCT CM 45...
Page 187: ...MCT CM 187...
Page 227: ...MCT CM 227 A 4 Control Module Specifications Main CPU...
Page 228: ...MCT CM 228...
Page 229: ...MCT CM 229...
Page 230: ...MCT CM 230...
Page 231: ...MCT CM 231 Analog I O Card...
Page 232: ...MCT CM 232...
Page 233: ...MCT CM 233 Digital Input Card...
Page 234: ...MCT CM 234...
Page 235: ...MCT CM 235 Digital Output Card...
Page 236: ...MCT CM 236...
Page 237: ...MCT CM 237 Dual Communications Card Barcode and Remote Display Communication Cartridges...
Page 238: ...MCT CM 238 A 5 Power Supply Specifications...
Page 239: ...MCT CM 239...
Page 240: ...MCT CM 240 A 6 Power On Delay Relay Specifications GE1A C10HA110...
Page 241: ...MCT CM 241...