MCT-CM
139
The redundancy settings
are accessed by selecting ‘Redundancy’ from the device settings ‘View’ menu. They
allow the user to set the redundancy mode of operation, select the primary system and adjust the concurrent
minimum runtime and/or alternating times. The user can also activate the product Load Timer which enables
the alarm inhibit of the OEM configured redundancy alarm. Consult your OEM configuration for the redundancy
type settings.
The redundancy
Status
indicates the current operating condition of redundancy. These include:
System 1/2 Inactive
= Redundancy not operating, control outputs off (system 1 and 2)
System 1 Active (automatic)
= Redundancy operating system 1 as primary system in auto
System 1 Active (manual)
= Redundancy operating system 1 as primary system in manual
System 2 Active (automatic)
= Redundancy operating system 2 as primary system in auto
System 2 Active (manual)
= Redundancy operating system 2 as primary system in manual
System 1 Active (fail Mode)
= Redundancy operating system 1 in auto, primary system 2 failed
System 2 Active (fail Mode)
= Redundancy operating system 2 in auto, primary system 1 failed
System 1/2 Active
= Redundancy operating system 1 and 2 concurrently (alarm activated)
System 1/2 Failed
= Redundancy operating, system 1 and 2 off (dual system failure)
The operational
Mode
selection indicates the redundancy mode and allows the user to place redundancy in
auto or manual operation. When in manual mode, only the primary system will operate and equal run time
switching will not take place. System failure alarm inputs and the redundancy process alarm are ignored. When
in auto mode, systems will perform equal run time switching based on user time settings and alternate
automatically upon system failure and redundancy process alarms.
The
Primary
system
selection allows the user to select system 1 or system 2 for operation. The primary system
selection can only be made when redundancy is placed in manual mode. When in auto mode, the primary
system selection will automatically alternate according to the alternating time settings.
The product
Load Timer
button allows the user to activate the alarm start delay of the OEM configured
redundancy process alarm. This alarm is one of the 30 alarms provided by the MCT and can be configured
by the user for process high/low, deviation or rate of change (see section 0
Summary of Contents for MCT-CM
Page 20: ...MCT CM 20...
Page 24: ...MCT CM 24...
Page 45: ...MCT CM 45...
Page 187: ...MCT CM 187...
Page 227: ...MCT CM 227 A 4 Control Module Specifications Main CPU...
Page 228: ...MCT CM 228...
Page 229: ...MCT CM 229...
Page 230: ...MCT CM 230...
Page 231: ...MCT CM 231 Analog I O Card...
Page 232: ...MCT CM 232...
Page 233: ...MCT CM 233 Digital Input Card...
Page 234: ...MCT CM 234...
Page 235: ...MCT CM 235 Digital Output Card...
Page 236: ...MCT CM 236...
Page 237: ...MCT CM 237 Dual Communications Card Barcode and Remote Display Communication Cartridges...
Page 238: ...MCT CM 238 A 5 Power Supply Specifications...
Page 239: ...MCT CM 239...
Page 240: ...MCT CM 240 A 6 Power On Delay Relay Specifications GE1A C10HA110...
Page 241: ...MCT CM 241...