8.2.1
Calculating Log File Size
The MCT saves the log file in a text-based format (.csv), so the amount of memory consumed for each reading
is dependent upon the number of digits required to accurately display the value (1 byte per character). This
optimizes memory usage but also makes calculating an exact file size difficult. To obtain a worst-case
approximation of the resultant file size, use the following formula:
File Size (Bytes) = (64 + LD) * number of readings in the file
Where:
LD (loop data) = 7 * number of points selected for logging
Example
MCT with ten loops of controller data (PV, SP, %Out selected) for each loop and 15 monitor points (PV)
selected (total of 45 points). Logging set at two second interval running for a duration of one day.
LD: 7 * 45 = 315
number of readings in file: 1 reading/2 secs * 60 secs/min * 60 mins/hr * 24 hrs/day = 86400
File Size (Bytes) = (64 + 315) * 43200 = 16,372,800
An MCT logging 45 points of data at a two second interval will consume a maximum of ~16MB of memory per
day. With an SD memory card size of 8GB, the MCT can log data continuously for over one year before the
SD memory card is full.
8GB = 8,000MB (total memory card space) / 16MB (per day) = 500 days (1.3 years)
NOTE:
Available memory space on the SD card is also affected by the number of ramp/soak programs, alarm
files and audit trail files that are stored. The quantity and size of these files will reduce the memory
space available for logging. Regular file maintenance is recommended in order to ensure adequate
space remains available for the logging of data.
8.3 Reviewing Historical Data
Historical files can be opened and viewed using the historical viewer. In order to view a historical data file, it
must first be opened by selecting
“Open” from the File menu. Once the file has been opened, the MCT can
automatically plot the first eight channels of the historical data file or the user can choose to cancel the plot and
select which channels should be plotted as well as adjust the specific time period to plot.
NOTE:
The open historical data file list will display up to 650 files. If more than 650 log files are present, the
files cannot be shown in the list and the files will have to be exported from the MCT in order to view
them. This can be done either via USB file utilities (see section 8.4 USB File Transfer) or FTP (see
section 8.5 FTP/FileWeb/DataWeb Interface).
8.3.1
History Plot Setup
The history plot setup allows the user to select any time frame (zoom in/out) from the historical data file as well
as select up to six channels of data to plot.
To edit the settings for the historical plot, select “Set” from the Chart
menu.
Summary of Contents for MCT-CM
Page 20: ...MCT CM 20...
Page 24: ...MCT CM 24...
Page 45: ...MCT CM 45...
Page 187: ...MCT CM 187...
Page 227: ...MCT CM 227 A 4 Control Module Specifications Main CPU...
Page 228: ...MCT CM 228...
Page 229: ...MCT CM 229...
Page 230: ...MCT CM 230...
Page 231: ...MCT CM 231 Analog I O Card...
Page 232: ...MCT CM 232...
Page 233: ...MCT CM 233 Digital Input Card...
Page 234: ...MCT CM 234...
Page 235: ...MCT CM 235 Digital Output Card...
Page 236: ...MCT CM 236...
Page 237: ...MCT CM 237 Dual Communications Card Barcode and Remote Display Communication Cartridges...
Page 238: ...MCT CM 238 A 5 Power Supply Specifications...
Page 239: ...MCT CM 239...
Page 240: ...MCT CM 240 A 6 Power On Delay Relay Specifications GE1A C10HA110...
Page 241: ...MCT CM 241...