background image

Description:

Quick Start Guide

HMC3043A-M

Specifications:

The HMC3043A-M is a combination operator-based HMI (Human
Machine Interface) with built-in PLC (Programmable Logic
Controller) operation. It communicates with external PLCs over
serial communications ports to read/write data. One I/O
expansion module can be attached.

Power:

 24VDC +/- 15%, 8W (with 1
expansion)

Display:

4.3” TFT (480 x 272 pixels)
Color graphics display

Bezel:

NEMA 4X (IP 66) rated

Touchscreen:

4-wire analog resistive

LEDs:

One Power LED

CPU:

32-bit RISC, 454 MHz

Port Details (COM1 and COM2):

DE9S (Female) Connector

Note: This model has one physical connector that can be used as

COM1 (RS232) and COM2 (RS485/422) simultaneously, when a

HMC3043A-M 480x272 pixels, 4.3” color TFT, with one expansion
slot, an Ethernet port, and two serial ports* (see note under

pinout).

Memory:

45 MB Max. Application Memory

Ethernet (RJ45):

One 10/100 Mbps port

Serial ports (DE9S):

Two serial ports

“Y” adapter cable is used. Connect shell to shield of cable.

Grounding:

USB Slave (Micro Type B):

(RS232/RS485/RS422)

The HMC3043 should have a good electrical connection to earth

Contents:

Upload/download projects

USB Host (Standard Type A):

ground via the power connector for safety and to reduce electrical

1 HMC3043A-M (in plastic bag with protective cover sheet

on the screen)

SD card:
Expansion ports:

Data storage

Micro SD (high capacity: 4-32 GB)

HMC3 I/O

noise. The HMC unit should be grounded separately from other
high-power systems.

1 plastic bag containing 4 mounting clamps (each clamp

consisting of cap nut, bolt, and clamp)

1 three prong green power plug*

Cardboard package inserts

One for optional

modules

Operating temp:

0 to 60° C

Humidity:

10% to 90% (non-condensing)

Dimensions (WxHxD):

4.72 x 3.50 x 1.24 inches

Quick Start Guide

*Note: Connector manufacturer may vary.

Programming software (MAPware-7000), cables, and power
supply purchased separately.

Panel Mounting and Panel Cutout:

Panel cutout:

Mounting Unit to Panel:

[120 x 89 x 31.5mm]
4.37 x 3.14 inches [111 x 80mm]

Note: Do not use a ground connection that has potential
impedance (such as painted screws) or is subject to vibration.

Expansion I/O Modules:

The HMC3043A-M has one expansion slot that you can use to
connect I/O modules. Below is a listing of modules currently
available (consult Maple Systems website for additional
information).

HMC3-M1616P:

 16 digital input, 16 PNP-type digital
output

Tighten the mounting screws evenly to a torque between 0.4 and 0.5
Nm to maintain water and dust resistance. Make sure the panel is not

dirty and warped and that it is strong enough to hold the unit.

Note: Maximum panel thickness (on which unit is to be mounted)
should be 6.0 mm (Tolerance: +/-0.2 mm).

Step 1: Place unit into cutout of panel and position mounting
clamps (4) into the side slots of HMC3043 enclosure as shown.

Step 2: Tighten clamps evenly to prevent warping. Continue to
tighten until a torque force of 0.4-0.5 Nm is obtained.

Step 3: HMC3043 should be aligned evenly with the cutout with
no warping present after clamps are tightened.

HMC3-M1614Y:

16 digital input, 14 digital output

(12 relay, 2 PNP-type)

HMC3-M1212P0200:

12 digital input, 12 PNP-type digital

output, 2 analog input

HMC3-M1212Y0200:

12 digital input, 12 digital output

(10 relay, 2 PNP-type), 2 analog
input

HMC3-M1210P0201:

12 digital input, 10 PNP-type digital

output, 2 analog input and 1 analog
output.

HMC3-M1210Y0201:

12 digital input, 10 digital output (8

relay, 2 PNP-type), 2 analog input,
and 1 analog output.

HMC3-M0808P0401T: 

8 digital input, 8 PNP-type digital

output, 4 analog input and 1 analog
output.

HMC3-M0808Y0401T: 

8 digital input, 8 digital output (6

relay, 2 PNP-type), 4 analog input,
and 1 analog output.

Doc. No. 1011-0301

Maple Systems, Inc. 808 134th St SW, Suite 120, Everett, WA 98204-7333   www.maplesystems.com

Rev 02, 11/29/2018

Reviews: