1 Rapid Link system 5
1.5 UL Standards Compliance
22
Rapid Link 5 · RAMO5 · RASP5
10/19 MN034004EN
www.eaton.com
1.5 UL Standards Compliance
1.5.1 RAMO5
The RAMO5 motor starters have been tested in accordance with
UL 60947-4-2 and are approved as “listed”.
Table 3:
RAMO5
Table 4:
Short circuit current rating for individual and group protection
The RAMO5 motor starter may be installed and operated observing following
conditions: The device is suitable for use on a circuit capable of delivering not
more than 65000 rms Symmetrical Amperes, 480 V:
•
When protected by 30 A fuses; or
•
when protected by a circuit breaker having an interrupting rating not less
than 65,000 rms Symmetrical Amperes, 480 Volts,32 A maximum.
Use with drives with flexible cables is subject to AHJ. Installation may be
limited to NFPA 79 applications.
Property
Value
Input voltage
480 V AC
Output voltage
480 V AC
Rated operating voltage for brake control
180 V DC / 230/480 V AC / 400/480 V AC
Input current
6,6 A
Output current
6,6 A
Phases
3
Frequency
50/60 Hz
Control voltage, external
24 V DC
Field bus input voltage
30 V DC
Motor protection
integrated
Thermistor monitoring
integrated
SCCR
Degree of protection
IP65/NEMA 12
Ambient temperature, maximum
55
°
C
With fuse (UL listed)
Circuit-breakers (UL listed)
with built-in
local discon-
nect switch
without built-
in local
disconnect
switch
with built-in
local discon-
nect switch
without built-
in local
disconnect
switch
Voltage
480 V AC
480 V AC
480 V AC
480 V AC
Short-circuit current,
maximum
30 A
30 A
32 A
32 A
Interrupting Rating
10 kA
65 kA
10 kA
10 kA
→
Devices with an integrated disconnect switch are approved for
use as “motor disconnects” (“lockout/tagout”).
Summary of Contents for Rapid Link RAMO5
Page 1: ...Manual Rapid Link 5 RAMO5 RASP5 10 19 MN034004EN ...
Page 4: ...II ...
Page 10: ...6 Rapid Link 5 RAMO5 RASP5 10 19 MN034004EN www eaton com ...
Page 122: ...4 Operation 4 3 Manual control 118 Rapid Link 5 RAMO5 RASP5 10 19 MN034004EN www eaton com ...
Page 158: ...8 PC tool 8 2 Parameter Editor 154 Rapid Link 5 RAMO5 RASP5 10 19 MN034004EN www eaton com ...
Page 208: ...11 Communications 11 5 OP Bus 204 Rapid Link 5 RAMO5 RASP5 10 19 MN034004EN www eaton com ...