10 Parameter list
10.3 Parameter groups for RAMO
Rapid Link 5 · RAMO5 · RASP5
10/19 MN034004EN
www.eaton.com
169
10.3.5 Parameter group 5 (“Communication”)
Table 31:
Parameter group 5 (“Communication”)
Para
meter
Designation
Description
Unit
Min
Max
DS
P5-01
RS485-0 Address
Unique address of the drive (keypad, OP bus)
–
1
63
1
P5-02
COM Loss Timeout
With an active communication link, if a valid telegram is
not received by the drive within the period set with this
parameter, the drive will react as set in P5-03.
s
0
5.0
2
P5-03
Action@Communication Loss
Device reaction after occuring of “Communication Loss”.
Possibilities device dependent
0: Trip
1: Ramp to stop, then trip
2: Ramp to stop only (no trip)
3: Run at preset speed 2 (P2-01)
–
0
2
0
P5-05
NETSendPZD3
Configuration of the 3rd process data word PDO-3 from the
drive to the network master during cyclic communication.
0: Motor current in A with one decimal place,
e.g. 100
≙
10.0 A
1: Output power in kW with 2 decimal places,
e.g. 400
≙
4.00 kW
2: Status of the digital inputs (DI). Bit 0 = Status DI1, Bit 1
= Status DI2 …)
3: Heatsink temperature. 0 - 100
≙
0 - 100 °C
4: User register 1. Configuration with Function Block Editor
5: User register 2. Configuration with Function Block Editor
6: P0-59 value (Selection via P5-09)
–
0
6
0
P5-06
NETSendPZD4
Configuration of the 4th process data word PDO-4 from the
drive to the network master during cyclic communication.
0: Motor current in A with one decimal place, e.g. 100
≙
10.0 A
1: Output power in kW with 2 decimal places, e.g. 400
≙
4.00 kW
2: Status of the digital inputs (DI). Bit 0 = Status DI1, Bit 1
= Status DI2 …)
3: Heatsink temperature. 0 - 100
≙
0 - 100 °C
4: User register 1. Configuration with Function Block Editor
5: User register 2. Configuration with Function Block Editor
6: P0-59 value (Selection via P5-09)
–
0
6
1
P5-07
NETReceivePZD3
Configuration of the 3rd process data word PDI-3 from the
network master to the drive during cyclic communication.
0: reserved
1: User defined ramp times with 2 decimal places
2: User register 3. Configuration with Function Block Editor.
3: User register 4. Configuration with Function Block Editor.
–
0
3
0
P5-08
NETReceivePZD4
Configuration of the 4th process data word PDI-4 from the
network master to the drive during cyclic communication.
0: reserved
1: User defined ramp times with 2 decimal places
2: User register 3. Configuration with Function Block Editor.
3: User register 4. Configuration with Function Block Editor.
–
0
3
0
Summary of Contents for Rapid Link RAMO5
Page 1: ...Manual Rapid Link 5 RAMO5 RASP5 10 19 MN034004EN ...
Page 4: ...II ...
Page 10: ...6 Rapid Link 5 RAMO5 RASP5 10 19 MN034004EN www eaton com ...
Page 122: ...4 Operation 4 3 Manual control 118 Rapid Link 5 RAMO5 RASP5 10 19 MN034004EN www eaton com ...
Page 158: ...8 PC tool 8 2 Parameter Editor 154 Rapid Link 5 RAMO5 RASP5 10 19 MN034004EN www eaton com ...
Page 208: ...11 Communications 11 5 OP Bus 204 Rapid Link 5 RAMO5 RASP5 10 19 MN034004EN www eaton com ...