10 Parameter list
10.4 Parameter groups for RASP
186
Rapid Link 5 · RAMO5 · RASP5
10/19 MN034004EN
www.eaton.com
10.4.7 Parameter group 6 (“Extended motor control”)
Table 40:
Parameter group 6 (“Extended motor control”)
Para-
meter
Designation
Description
Unit
Min
Max
DS
P6-01
Motor Control Mode
Motor Control Mode
An autotune must be performed if setting 1 / 2 / 3 / 4 / 5 is
used
0: Smart-Vector Speed Control
1: Speed Control with Torque Limit (vector)
2: PM Motor Speed Control
3: LSPM Motor Speed Control
4: SyncRel Motor Speed Control
5: Brushless DC Motor Speed Control
6: Speed Control (enhanced V/f)
–
0
6
0
P6-02
MSC Kp
Proportional gain Kp at Motor Speed Control
(P4-01 = 0, 3, 5, 6)
%
0.0
400.0
50.0
P6-03
MSC1 Ti
Integral time Ti at Motor speed Control
(P4-01 = 0, 3, 5, 6)
s
0.010
1.000
0,050
P6-04
M-Max Motoring
M-Max Motoring
When working in Vector mode (P4-01 = 1) this parameter
defines the max. torque limit. In the remaining control
modes, this parameter specifies the current limit.
%
0
200%
150%
P6-05
Action@Underload Motor
Device reaction after occuring of “Underload Motor”.
Possibilities device dependent
0 = deactivated
1 = Warning
2 = Trip (stop)
–
0
1
0
P6-06
M-Min (f-Ref=0) Limit
Minimum torque allowed with zero frequency.
%
10
150
50
P6-07
M-Min (f>f-Vmax) Limit
Minimum torque allowed when the output frequency is
above the field weakening point.
%
5
150
10
P6-08
Change Phasesequence Motor
Changes the sequence of the output phases.
This prevents, that two phases of the motor cable have to
be changed in case the motor runs in the wrong direction.
0 = U, V, W (cw)
1 = U, W, V (ccw)
Note:
Only with RASP5… and RAMO5-W…
–
0
1
0
P6-09
T-Memory Enable
When enabled, the motor thermal memory retention func-
tion will save the calculated motor thermal history on drive
power down, using this saved value as the starting value
on next power up. If this function is disabled, the motor
thermal history is reset to zero on every power up.
0: Thermal memory OFF
1: Thermal memory ON
-
0
1
1
P6-10
Action @I-CurrentLimit
0: deactivated - motor overload management switched off
1: activated - speed decrease
The output torque is reduced to avoid overload.
P6-11
EnhancedGeneratorControl
EnhancedGeneratorControl
Adaptation of the motor model in vector mode and with PM
motors to achieve a better performance of the drive when
regenerating.
0: disable
1: enable
-
0
1
0
Summary of Contents for Rapid Link RAMO5
Page 1: ...Manual Rapid Link 5 RAMO5 RASP5 10 19 MN034004EN ...
Page 4: ...II ...
Page 10: ...6 Rapid Link 5 RAMO5 RASP5 10 19 MN034004EN www eaton com ...
Page 122: ...4 Operation 4 3 Manual control 118 Rapid Link 5 RAMO5 RASP5 10 19 MN034004EN www eaton com ...
Page 158: ...8 PC tool 8 2 Parameter Editor 154 Rapid Link 5 RAMO5 RASP5 10 19 MN034004EN www eaton com ...
Page 208: ...11 Communications 11 5 OP Bus 204 Rapid Link 5 RAMO5 RASP5 10 19 MN034004EN www eaton com ...