3 Installation
3.6 Motor feeder
Rapid Link 5 · RAMO5 · RASP5
10/19 MN034004EN
www.eaton.com
103
3.6.4 Screened motor cable for RASP5.
3.6.4.1 General notes
The following information uses the example of a DESINA MOTORFLEX cable
with 4G1.0 2 x (2 x 0.75), to describe the steps required for the EMC connec-
tion of a mains cable to the RASP5.
Figure 67: EMC-compliant connection of the screened motor cable
a
360° contact fuse
≙
power
▶
Stripping the motor cable ends (radial and longitudinal cut).
▶
Push the screen braid back to reveal the individual conductors.
▶
The conductors B1 (= N) and B2(= L) for the external brake as well as T1
and T2 for the thermistor have a sheath and a separate screen braid.
These conductors must be stripped separately.
▶
Then slide the outer screen braid of the motor cable back toward the
cable end far enough that conductors B1/B2 and T1/T2 are covered over
a large area and connected with each other.
→
To strip the cable, set the blade so that the conductor insulation
and the screen braid remain undamaged.
→
Wrap insulating or textile tape or slide a rubber grommet around
the screen ends to prevent the screen braid from splicing.
U1, V1, W1, PE
B1/B2
T1/T2
①
Summary of Contents for Rapid Link RAMO5
Page 1: ...Manual Rapid Link 5 RAMO5 RASP5 10 19 MN034004EN ...
Page 4: ...II ...
Page 10: ...6 Rapid Link 5 RAMO5 RASP5 10 19 MN034004EN www eaton com ...
Page 122: ...4 Operation 4 3 Manual control 118 Rapid Link 5 RAMO5 RASP5 10 19 MN034004EN www eaton com ...
Page 158: ...8 PC tool 8 2 Parameter Editor 154 Rapid Link 5 RAMO5 RASP5 10 19 MN034004EN www eaton com ...
Page 208: ...11 Communications 11 5 OP Bus 204 Rapid Link 5 RAMO5 RASP5 10 19 MN034004EN www eaton com ...