2 Engineering
2.8 STO function
Rapid Link 5 · RAMO5 · RASP5
10/19 MN034004EN
www.eaton.com
49
2.8.3 STO-compatible installation
DANGER
Make sure to use proper grounding and select cables based on
local regulations or standards.
The variable frequency drive may have a leakage current greater
than 3.5 mA AC or 10 mA DC. In addition, the grounding cable
must be sized for the maximum mains fault current, which is
normally limited by fuses or miniature circuit-breakers.
Appropriately sized fuses or miniature circuit-breakers should be
installed at the mains supply for the variable frequency drive in
line with local regulations or standards.
DANGER
The “STO wiring” must be protected against unintended short-
circuits and unintended tampering and modifications.
It must be ensured that the “STO input signal” has a safe oper-
ating state.
→
In order to prevent damage to the variable frequency drive,
the devices should remain in their original packaging until right
before they are installed.
They must be stored in a dry and clean area with a temperature
range of -40 °C to 60 °C.
→
The conductor cross-section used for the STO installation
should be between 0.75 and 2.5 mm
2
.
The length of the cable connected to the control signal terminals
should not exceed 25 meters.
Summary of Contents for Rapid Link RAMO5
Page 1: ...Manual Rapid Link 5 RAMO5 RASP5 10 19 MN034004EN ...
Page 4: ...II ...
Page 10: ...6 Rapid Link 5 RAMO5 RASP5 10 19 MN034004EN www eaton com ...
Page 122: ...4 Operation 4 3 Manual control 118 Rapid Link 5 RAMO5 RASP5 10 19 MN034004EN www eaton com ...
Page 158: ...8 PC tool 8 2 Parameter Editor 154 Rapid Link 5 RAMO5 RASP5 10 19 MN034004EN www eaton com ...
Page 208: ...11 Communications 11 5 OP Bus 204 Rapid Link 5 RAMO5 RASP5 10 19 MN034004EN www eaton com ...