1.4 Technical data
20
Rapid Link 5 · RAMO5 · RASP5
10/19 MN034004EN
www.eaton.com
Main circuit
Supply
Rated operational voltage
U
e
V
3 AC 400/480
3 AC 400/480
Rated operating voltage for brake
control
U
e
V
180 V DC
230/277 V AC
400/480 V AC
180 V DC
230/277 V AC
400/480 V AC
Voltage range
U
LN
V
380 - 10% - 480 + 10%
380 - 10% - 480 + 10%
Frequency range
f
LN
Hz
(50 - 10 %) - (60 + 10 %)
50/60 (45 - 66 Hz ±0 %)
Network type
Alternating voltage, center-point-
earthed star network (TN-S network)
Phase-earthed AC supply systems are
not permitted.
Alternating voltage, center-point-
earthed star network (TN-S network)
Phase-earthed AC supply systems are
not permitted.
Mains switch-on frequency
Quantity
max. one time per minute
max. one time per minute
Mains current
THD
%
< 120
< 120
short-circuit current
I
K
kA
< 10
< 10
Short-circuit protection device
(Power bus incoming unit)
PKE3/XTUCP-36
FAZ-3-B20 or FAZ-3-C20
PKE3/XTUCP-36
FAZ-3-B20 or FAZ-3-C20
Overvoltage category/
pollution degree (DIN/VDE 0110)
III
III
Rated impulse withstand voltage
U
imp
kV
4
–
Leakage current to PE earth (EN 50178)
I
PE
mA
< 3.5
< 3.5
Power section
Instance
RAMO5-D: Direct-on-line starter with
thyristors and bypass contacts
Frequency inverter with internal DC
link and IGBT inverter
RAMO5-W: Reversing starter with
relay, thyristors and bypass contacts
two-phase controlled
Service life (AC3)
Quantity
> 10 millions connections
–
Output voltage
U
2
V AC
0 - U
LN
0 - U
LN
Output frequency
f
2
Hz
0 - 50/60 Hz
0 - 50 Hz, max. 500 Hz
Rated current
I
e
A
6.6
2.4 / 4.3 / 5.6 / 8.5
Load current for the control unit for an
external brake
I
A
≦
0.6
600 mA constant, 6 A for 120 ms
≦
0.6
600 mA constant, 6 A for 120 ms
Adjustable motor protection
I
A
0.3 - 6.6
0.48 - 8.5
Overload withstand capability
for 60 s every 600 s at +40
°
C
I
L
%
–
150
for 2 s every 20 s at +40
°
C
I
H
%
–
200
Assigned motor output
1)
P
kW
(with motor protection) with 400
V,
50
Hz
P
kW
0.18 - 4
0.18 - 4
at 440 V - 460 V, 60 Hz
P
HP
0.25 - 5
0.25 - 5
Technical data
Formula
sign
Unit
Value
RAMO5
RASP5
Summary of Contents for Rapid Link RAMO5
Page 1: ...Manual Rapid Link 5 RAMO5 RASP5 10 19 MN034004EN ...
Page 4: ...II ...
Page 10: ...6 Rapid Link 5 RAMO5 RASP5 10 19 MN034004EN www eaton com ...
Page 122: ...4 Operation 4 3 Manual control 118 Rapid Link 5 RAMO5 RASP5 10 19 MN034004EN www eaton com ...
Page 158: ...8 PC tool 8 2 Parameter Editor 154 Rapid Link 5 RAMO5 RASP5 10 19 MN034004EN www eaton com ...
Page 208: ...11 Communications 11 5 OP Bus 204 Rapid Link 5 RAMO5 RASP5 10 19 MN034004EN www eaton com ...