10 Parameter list
10.3 Parameter groups for RAMO
Rapid Link 5 · RAMO5 · RASP5
10/19 MN034004EN
www.eaton.com
165
10.3.2 Parameter group 1 (“Basic”)
Table 28:
Parameter group 1 (“Basic”)
Para-
meter
Designation
Description
Unit
Min
Max
DS
P1-08
Motor Nom Current
Motor rated current.
By setting the ”Motor Nom Current” in the drive, the motor
overload protection is configured to match the motor
rating.
When the measured motor current exceeds “Motor Nom
Current”, the decimal points on the display will flash to
indicate an overload condition.
If this condition persists, the drive will eventually trip,
displaying
I.t-trP
, preventing thermal overload of the
motor.
Amps
0.3
6.6
6.6
P1-13
DI Config Select
Configuration of digital inputs with a fix set of combina-
tions
–
1
4
1
P1-14
Access Key
Entry of the password to get access to the extended
parameter set.
The value to be put in is determined by the level to be
accessed.
Level 2 (Access to parameter groups 0 to 8): P1-14 = P2-32
(Default: 101)
–
0
65535
0