11.4 Diagnostics and troubleshooting via AS-Interface
All faults identified by the power module (DQL) are internally transmitted to
the AS-Interface component as group fault messages:
Di = 0 (Low). The red LED in the motor symbol lights up.
▶
Turn the key switch to the OFF position to reset the error message.
Hold the switch in this position for at least one second so that the
RAMO5 unit will detect the command.
The Reset signal via AS-i provides an additional reset option for RAMO5 units
in case the latter cannot be locally reset due to accessibility issues.
The local reset via the keyswitch remains the main application, as each
diagnosis has a cause that needs to be analyzed and eliminated on-site.
Table 47:
RAMO5 internal diagnostic status (for briefed service personnel only)
The unit can be switched back on after approximately one minute.
If the fault continues to be present, the motor LED will show a solid red light.
If the error is corrected within this time, the red motor LED flashes. A reset
must then be performed via the key switch.
Diagnostics status
Status
Accumu-
lative
error
Peripheral
error (FID)
Explanation
P1
P2
P3
P4
1)
DI1
Thyristor/bypass contact
defective
0
0
1
0
0
1
Output switched through (On position) without actuation
signal
Possible causes:
• Thyristor failed
• Bypass contact welded
• I3/I4 sensor short-circuit
• actuator short-circuit
Overload release
0
1
0
0
0
0
Triggering at 110 % of the thermal motor simulation value
Thermistor tripping
0
1
1
0
0
0
Possible causes:
Motor plug not plugged
• Thermistor in motor not connected
• Jumper in terminal box of motor or in motor feeder plug
missing (T1 = Pin 5, T2 = Pin 8).
• Tripping due to excessive resistance in thermistor sensor
circuit (e.g. overtemperature)
No diagnostic alarm
1
1
1
0
0
0
Possible causes:
• Overload or short-circuit of external inputs I3, I4
• Overload or short-circuit of external output
• Incorrect DIP switch setting
• Supply voltage 400 V missing
• Trip in event of undershooting current lower limit
Manual mode
(status_local_operation)
1
0
0
0
1
0
Key-switch in MANUAL (HAND) position
Load message 1
(status_overload_warning)
1
0
1
0
1
0
Message at 90 % of thermal motor simulation value
(preventive maintenance, message reset automatically).
Load message 2
(status_load_indication)
1
1
0
1
1
0
Message at 70 % of thermal motor simulation value
(preventive maintenance; message will be reset automati-
cally).
1) P4 diagnostics possible only with standard slave profile (S-7.4)
Summary of Contents for Rapid Link RAMO5
Page 1: ...Manual Rapid Link 5 RAMO5 RASP5 10 19 MN034004EN ...
Page 4: ...II ...
Page 10: ...6 Rapid Link 5 RAMO5 RASP5 10 19 MN034004EN www eaton com ...
Page 122: ...4 Operation 4 3 Manual control 118 Rapid Link 5 RAMO5 RASP5 10 19 MN034004EN www eaton com ...
Page 158: ...8 PC tool 8 2 Parameter Editor 154 Rapid Link 5 RAMO5 RASP5 10 19 MN034004EN www eaton com ...
Page 208: ...11 Communications 11 5 OP Bus 204 Rapid Link 5 RAMO5 RASP5 10 19 MN034004EN www eaton com ...