5 RAMO5 Motor starter
5.7 Configure special settings
Rapid Link 5 · RAMO5 · RASP5
10/19 MN034004EN
www.eaton.com
131
5.7.5 Monitoring the current lower limit
When P6-05 = 1 (= ON ), an error message (the motor LED will light up red)
will be output when a phase (L1, L2, L3) carries less than 25 % of rated oper-
ational current l
e
.
5.7.6 Quick Stop
The quick-stop function is performed via DQ3 (ASi signal).
The function can be activated via parameter P5-10.
Parameter
Designation
Description
Unit
Min
Ma
x
DS
P6-05
Underload Protection
Device response (depending on device) after “underload motor”
occurs.
0 = deactivated
1 = Warning
2 = Error (shutdown)
–
0
1
0
Parameter
Designation
Description
Unit
Min
Max
DS
P5-10
QuickStop lock
0: Quick stop via sensors deactivated.
1: Quick stop via sensors activated (ASi signal active).
–
0
1
0
P5-10
DQ3
Function
Description
1
0
Quick stop ON
Response to sensors
1
1
Quick stop OFF
No response to sensors
0
0
None
DQ3 signals will not be transmitted
0
1
None
DQ3 signals will not be transmitted
Summary of Contents for Rapid Link RAMO5
Page 1: ...Manual Rapid Link 5 RAMO5 RASP5 10 19 MN034004EN ...
Page 4: ...II ...
Page 10: ...6 Rapid Link 5 RAMO5 RASP5 10 19 MN034004EN www eaton com ...
Page 122: ...4 Operation 4 3 Manual control 118 Rapid Link 5 RAMO5 RASP5 10 19 MN034004EN www eaton com ...
Page 158: ...8 PC tool 8 2 Parameter Editor 154 Rapid Link 5 RAMO5 RASP5 10 19 MN034004EN www eaton com ...
Page 208: ...11 Communications 11 5 OP Bus 204 Rapid Link 5 RAMO5 RASP5 10 19 MN034004EN www eaton com ...