5 RAMO5 Motor starter
5.6 LED displays
126
Rapid Link 5 · RAMO5 · RASP5
10/19 MN034004EN
www.eaton.com
I2
Sensor input SI2
Off
• not connected
• Not triggered (no input signal)
Green
SI2 triggered (input signal)
Q1
Actuator output Q1
Only for
RAMO5-xx1…
!
Off
• Not actuated
Green
Q1 triggered (output signal)
Note:
If the external supply voltage for Q1 (24 V DC)
is missing, no signal is applied at the output.
PWR
Off
The 400 V supply voltage is missing or the repair switch is switched off.
Green
Supply voltage 400 V
RAMO group fault indication
Off
No fault message
FLT
Red
Fault message:
An error has been detected and is permanently present - in the case of:
• Motor overload (overcurrent)
→
Check motor and drive unit
(reset with engine cooled down)
≥
parameters
→
Check short shot in motor lead
→
parameters
• Thermistor/cable monitoring
→
Check motor and drive unit
(reset when motor has cooled down)
→
No motor cable connected (motor outgoer socket)
→
Wire jumper not closed with motor cable disconnected
(
→
for servicing only)
• Overload/short circuit on sensor inputs or actuator output
On a temporary or rectified fault this LED flashes until the Reset command is
issued.
Flashing
(red)
The detected fault (the fault signal's cause) has been fixed.
The fault signal can now be acknowledged with key switch OFF/RESET
(
→
The LED
FLT
goes out).
LED
State
Description
REV
OFF
FWD
PWR
FLT
SEN I1
I1
ACT Q1
Q1
SEN I2
I2
AS-I
Data
Fault
OFF/RESET
Summary of Contents for Rapid Link RAMO5
Page 1: ...Manual Rapid Link 5 RAMO5 RASP5 10 19 MN034004EN ...
Page 4: ...II ...
Page 10: ...6 Rapid Link 5 RAMO5 RASP5 10 19 MN034004EN www eaton com ...
Page 122: ...4 Operation 4 3 Manual control 118 Rapid Link 5 RAMO5 RASP5 10 19 MN034004EN www eaton com ...
Page 158: ...8 PC tool 8 2 Parameter Editor 154 Rapid Link 5 RAMO5 RASP5 10 19 MN034004EN www eaton com ...
Page 208: ...11 Communications 11 5 OP Bus 204 Rapid Link 5 RAMO5 RASP5 10 19 MN034004EN www eaton com ...