10 Parameter list
10.4 Parameter groups for RASP
Rapid Link 5 · RAMO5 · RASP5
10/19 MN034004EN
www.eaton.com
177
P1-09
Motor Nom Frequency
The rated frequency of the motor.
This is the frequency at which ”Motor Nom Voltage” is
applied to the motor.
Below this frequency, the applied motor voltage will be
reduced. Above this frequency the voltage remains limited
to ”Motor Nom Voltage”.
Hz
10
500
50 (60)
P1-10
Motor Nom Speed
Motor rated speed
P1-10 = 0: the speed of the motor will be displayed in Hz.
P1-10 > 0: the speed related parameters (f-max, f-min etc.)
will be displayed in rpm.
The slip compensation is also activated, where the shaft
speed of the motor is maintained under varying load condi-
tions by compensating for the load-dependent slip of the
motor.
If “Motor Nom Speed” = motor synchronous speed (e.g.
3000 rpm for a 2-pole 50 Hz motor), the speed can be
displayed in rpm without activating the slip compensation.
rpm
0
30000
0
P1-11
V-Boost
Voltage is used to increase the applied motor voltage at
low output frequency, in order to improve low speed and
starting torque.
Excessive voltage boost levels may result in increased
motor current and temperature, and forced ventilation may
be required.
An automatic setting (Auto) is also possible, whereby the
drive will automatically adjust this parameter based on the
motor parameters measured during an Autotune.
%
0
40
0
P1-12
f-Fix1
Preset Fixed Frequency 1
Value can be adjusted between f-min and f-max.
Selection via a digital control signal.
Hz
P1-02
P1-01
10.0Hz
P1-13
DI Config Select
Configuration of digital inputs with a fix set of combina-
tions
0
12
1
P1-14
Access Key
Entry of the password to get access to the extended
parameter set.
The value to be put in is determined by the level to be
accessed.
Level 2 (Access to parameter groups 0 to 8): P1-14 = P2-32
(Default: 101)
–
0
65535
0
Para-
meter
Designation
Description
Unit
Min
Max
DS
Summary of Contents for Rapid Link RAMO5
Page 1: ...Manual Rapid Link 5 RAMO5 RASP5 10 19 MN034004EN ...
Page 4: ...II ...
Page 10: ...6 Rapid Link 5 RAMO5 RASP5 10 19 MN034004EN www eaton com ...
Page 122: ...4 Operation 4 3 Manual control 118 Rapid Link 5 RAMO5 RASP5 10 19 MN034004EN www eaton com ...
Page 158: ...8 PC tool 8 2 Parameter Editor 154 Rapid Link 5 RAMO5 RASP5 10 19 MN034004EN www eaton com ...
Page 208: ...11 Communications 11 5 OP Bus 204 Rapid Link 5 RAMO5 RASP5 10 19 MN034004EN www eaton com ...