3 Installation
3.6 Motor feeder
104
Rapid Link 5 · RAMO5 · RASP5
10/19 MN034004EN
www.eaton.com
▶
At the motor’s terminal box, connect the motor cable’s braid to ground
potential (PES).
Figure 68: 360° screen contact at the motor terminal box
a
360° contact screen for the motor cable
b
Clamp strap with screw for the screen braid
▶
Connect the jointly twisted strands (U, V, W, and PE) and separately
twisted strands B1/B2 and T1/T2 to the corresponding terminals in the
motor or in the connector.
The substrate must be free from varnish (direct contacting).
The screen clamp shown in the illustration is an example of a large-area
ground connection (PES).
Figure 69: Connecting a screen braid (PES)to the motor terminal box
b
a
a
U
V
W
U V W PE
PE
PES