10 Parameter list
10.4 Parameter groups for RASP
Rapid Link 5 · RAMO5 · RASP5
10/19 MN034004EN
www.eaton.com
183
10.4.5 Parameter group 4 (“Brake chopper and DC brake”)
Table 38:
Parameter group 4 (“Motor braking”)
Para-
meter
Designation
Description
Unit
Min
Max
DS
P4-01
DC-Brake Current
DC braking is active in all control modes (P6-01 = 0, …, 6)
and with any stop mode (P1-05 = 0, 1, 2).
To enable DC current injection at START set a DC braking
current (P4-01) and a DC braking time at start (P4-02).
After receiving the start signal the Drive injects a DC
current (P4-01) for the time specified at P4-02. After P4-02
times-out, drive resumes normal operation.
To enable DC current injection at STOP set a DC braking
current (P4-01), a DC braking time (P4-04) and a DC braking
frequency (P4-03).
When the drive receives the STOP command, it will start to
decelerate down to 0. As soon as it reaches the frequency
set in P4-03, the drive will start to inject a DC current
(P4-01) for the time specified at P4-04.
After P4-04 times out, PWM is disabled, drive status
changes to STOP. If coast to stop is selected, DC injection
is executed just after receiving the stop command.
%
0
100%
0
P4-02
t-DCBrake@Start
Duration of DC braking before Start
s
0
600
0
P4-03
f-DCBrake@Stop
Output frequency in Hz at which DC braking starts during
the deceleration phase.
Hz
0
10
1.5
P4-04
t-DCBrake@Stop
Duration of DC braking at Stop
s
0
600
0
P4-05
Brake Chopper Mode
Parameter function only for devices with internal brake
resistor
0: deactivated
1: active in RUN
2: active in RUN and STOP
–
0
2
2
P4-06
Brake Resistor
Resistance of the brake resistor in Ohms
This value, together with P4-07, is used for the thermal
protection of the brake resistor.
With internal brake resistor, do not change the value.
ohms
50
500
400
P4-07
P-Brake Resistor
Power of the brake resistor in kW
Resolution 0.1 kW. This value, together with P4-06, is used
for the thermal protection of the brake resistor.
With internal brake resistor, do not change the value.
kW
0
20.00
0.1
P4-08
Brake Chopper ED Heat-Up
Brake Chopper Duty Cycle
At very low temperatures (< -10 °C) the drive doesn’t work
and indicates “Under temperature” (Fault code 09 “U-t”).
Devices with internal brake resistor can use this to heat up
the device. Parameter P4-08 determines the load cycle.
%
0
20.0
2.0
Summary of Contents for Rapid Link RAMO5
Page 1: ...Manual Rapid Link 5 RAMO5 RASP5 10 19 MN034004EN ...
Page 4: ...II ...
Page 10: ...6 Rapid Link 5 RAMO5 RASP5 10 19 MN034004EN www eaton com ...
Page 122: ...4 Operation 4 3 Manual control 118 Rapid Link 5 RAMO5 RASP5 10 19 MN034004EN www eaton com ...
Page 158: ...8 PC tool 8 2 Parameter Editor 154 Rapid Link 5 RAMO5 RASP5 10 19 MN034004EN www eaton com ...
Page 208: ...11 Communications 11 5 OP Bus 204 Rapid Link 5 RAMO5 RASP5 10 19 MN034004EN www eaton com ...