Configure > Parameters > [Busbar] > AC setup > Multiple phase wire break
Table 3.66
Default parameters
Parameter
Range
Default
Enable
Not enabled, Enabled
Enabled
Latch
Not enabled, Enabled
Enabled
Alarm action
Warning
3.7.2 [Source]/[Busbar] L# wire break
Controller types: GENSET, SHAFT generator, SHORE connection and BUS TIE breaker controllers
These alarms alert the operator to a measurement failure on a phase:
•
[Source] L1 wire break
•
[Source] L2 wire break
•
[Source] L3 wire break
•
[Busbar] L1 wire break
•
[Busbar] L2 wire break
•
[Busbar] L3 wire break
The controller only activates the alarm when all of these conditions are met:
•
The generator breaker is closed
•
Voltage is detected by one set of ACM voltage measurements
•
No voltage is detected on one of the phases for the other set of ACM voltage
measurements
0
1
Time
Busbar
L1
Wire break
L1
L2
L3
Generator
voltage
L1
L2
L3
Busbar
voltage
Parameters
Configure the [Source] parameters under
Configure > Parameters > [Source] > AC setup > L# wire break
, where # is 1, 2 or 3.
Configure the [Busbar] parameters under
Configure > Parameters > [Busbar] > AC setup > L# wire break
, where # is 1, 2 or 3.
Table 3.67
Default parameters
Parameter
Range
Default
Enable
Not enabled, Enabled
Enabled
Latch
Not enabled, Enabled
Enabled
Alarm action
Warning
3.8 ACM module general protections
3.8.1 ACM 1 protections not running
This alarm communicates that the configuration data for protections and measurements are not correct in the controller alternating
current module (ACM).