SHORE connection alarm
Configure > Parameters >
General name
Reverse power 1 or 2
Shore connection > Power protections > Reverse power 1 or
2
Reverse power
Reactive power export 1 or 2
Shore connection > Reactive power protections > Reactive
power export 1 or 2
Reactive power export
Reactive power import 1 or 2
Shore connection > Reactive power protections > Reactive
power import 1 or 2
Reactive power import
Table 11.21
Busbar AC alarm names for the SHORE connection controller
SHORE connection alarm
Configure > Parameters >
General name
Busbar over-voltage 1 or 2
Busbar > Voltage protections > Over-voltage 1 or 2
Busbar over-voltage
Busbar under-voltage 1 or 2
Busbar > Voltage protections > Under-voltage 1 or 2
Busbar under-voltage
Busbar voltage unbalance
Busbar > Voltage protections > Voltage unbalance
Busbar voltage unbalance
Busbar over-frequency 1 or 2
Busbar > Frequency protections > Over-frequency 1 or 2
Busbar over-frequency
Busbar under-frequency 1 or 2
Busbar > Frequency protections > Under-frequency 1 or 2
Busbar under-frequency
11.5.6 SC-DG max. parallel time
This alarm limits the time that a shore connection may run in parallel to a genset.
The timer starts when the genset or emergency genset is connected to the same
busbar as the shore connection.
Controller type: SHORE connection controller only.
G
SHORE
connection
The alarm can be configured under
Configuration > Parameters > Local power management > Parallel timers
. The action is
Trip
shore connection breaker
,
Latch enabled
.
Table 11.22
SC-DG max. parallel time parameters
Parameter
Range
Default
Delay
0.1 s to 1 h
3 min
Enable
Not enabled, Enabled
Enabled
More information
See
GENSET controller
,
GENSET controller protections
,
DG-SC max. parallel time
for the alarm in the GENSET
controller that trips the generator breaker.
11.5.7 SC-SG max. parallel time
DANGER!
Connecting a shaft generator to a shore connection can release a large amount of energy. This can kill people and destroy
equipment.
DESIGNER'S HANDBOOK 4189340911K UK
Page 398 of 521