Trip tie breaker
Controller type
EMERGENCY genset controller
Priority
High
Effect
The controller trips the tie breaker to the emergency busbar (that is, without de-loading).
Trip shore connection breaker
Controller type
SHORE connection controller
Priority
High
Effect
The controller trips the shore connection breaker (that is, without de-loading).
Trip bus tie breaker
Controller type
BUS TIE breaker controller
Priority
High
Effect
The controller trips the bus tie breaker (that is, without de-loading).
Trip generator breaker and stop engine
Controller types
GENSET and EMERGENCY genset controllers
Priority
High
Effect
The controller trips the genset breaker (that is, without de-loading). After the cooldown period, the
controller stops the engine.
Trip generator breaker and shutdown engine
Controller types
GENSET and EMERGENCY genset controllers
Priority
Highest
Effect
The controller trips the genset breaker (that is, without de-loading). The controller shuts down the
engine,
without
a cooldown period.
Trip AVR
Controller types
GENSET, EMERGENCY genset and SHAFT generator controllers
Priority
High
Effect
The controller trips the AVR (that is, stops voltage or reactive power regulation).
Trip generator b AVR
Controller types
GENSET, EMERGENCY genset and SHAFT generator controllers
Priority
High
Effect
The controller trips the genset or shaft generator breaker (that is, without de-loading) and the AVR
(that is, stops reactive power regulation).
Trip generator b AVR + stop engine
Controller types
GENSET and EMERGENCY genset controllers
Priority
High
Effect
The controller trips the genset breaker (that is, without de-loading) and the AVR (that is, stops
reactive power regulation). After the cooldown period, the controller stops the engine.