Parameter
Range
Default
Notes
•
Enabled
: During frequency regulation, the controller uses the
Frequency
offset [%]
analogue input or Modbus input to determine the frequency set
point.
Frequency offset
source
•
External
•
External -> Off
External
•
External
: The controller uses the
Frequency offset [%]
analogue input or
Modbus input.
•
External ->
Off
: If the
Frequency offset [%]
analogue input and/or Modbus
input fails (that is, when the input is outside the configured scale), then the
controller ignores the input.
P set point
enable
•
Not enabled
•
Enabled
Not
enabled
•
Not enabled
: The controller ignores the
Power set point [%]
analogue
input and Modbus input.
•
Enabled
: During power regulation, the controller uses the
Power set point
[%]
analogue input or Modbus input as the power set point.
P set point
source
•
External
•
External -> Off
External
•
External
: The controller uses the
Power set point [%]
analogue input or
Modbus input.
•
External ->
Off
: If the
Power set point [%]
analogue input and/or Modbus
input fails (that is, when the input is outside the configured scale), then the
controller ignores the input.
INFO
If an analogue input is configured, the Modbus value for the external offset will reflect the analogue input value. The
Modbus external offset cannot be configured until the analogue input for the external offset is cleared.
AVR parameters
You can configure the governor common settings under
Configure > Parameters > Regulators > AVR general configuration
.
INFO
To see these parameters, you must assign an AVR output function.
External offset
These parameters allow analogue inputs to determine the genset's voltage, reactive power or cos phi set point.
Parameter
Range
Default
Notes
Voltage offset
enable
•
Not enabled
•
Enabled
Not
enabled
•
Not enabled
: The controller ignores the
Voltage offset [%]
analogue input
and Modbus input.
•
Enabled
: During voltage regulation, the controller uses the
Voltage offset
[%]
analogue input or Modbus input to determine the voltage set point.
Voltage offset
source
•
External
•
External -> Off
External
•
External
: The controller uses the
Voltage offset [%]
analogue input or
Modbus input.
•
External ->
Off
: If the
Voltage offset [%]
analogue input and/or Modbus
input fails (that is, when the input is outside the configured scale), then the
controller ignores the input.
Q set point
enable
•
Not enabled
•
Enabled
Not
enabled
•
Not enabled
: The controller ignores the
Reactive power set point [%]
analogue input and Modbus input.
•
Enabled
: During reactive power regulation, the controller uses the
Reactive power set point [%]
analogue input or Modbus input as the
reactive power set point.
Q set point
source
•
External
•
External -> Off
External
•
External
: The controller uses the
Reactive power set point [%]
analogue
input or Modbus input.
•
External ->
Off
: If the
Reactive power set point [%]
analogue input and/or
Modbus input fails (that is, when the input is outside the configured scale),
then the controller ignores the input.
DESIGNER'S HANDBOOK 4189340911K UK