Category
Specification
Between analogue inputs and other I/Os: 600 V, 50 Hz for 60 s
Ingress protection
Unmounted: No protection rating
Mounted in rack: IP20 according to IEC/EN 60529
Size
L 28 mm × H 162 mm × D 150 mm (1.1 in × 6.4 in × 5.9 in)
Weight
250 g (0.5 lb)
13.9.2 EIM3.1 terminal overview
Terminal Symbol Name
Type
F/G
F/G
Ground
1
+
-
+
12 or 24 V DC (nominal)*
2
-
0 V DC
3
Normally open
Relay output (30 V DC and 6 A)
4
Common
5
Normally open
6
Common
7
Normally open
8
Common
9
*
Normally open
Relay output with wire break detection (30 V DC and 6 A)
10
Common
11
Bi-directional input
Digital input (OFF: 0 to 2 V DC, ON: 8 to 36 V DC, Impedance: 4.7 kΩ)
12
Bi-directional input
13
Bi-directional input
14
Bi-directional input
15
COM
Common
Common for digital input terminals 11 to 14
16
MPU input with wire btreak detection (Voltage: 2 to 70 V AC peak, Frequency: 2 to
20,000 Hz)
17
COM
Common
MPU or W input
18
W
W input (Voltage: 8 to 36 V AC, Frequency: 2 to 20,000 Hz)
19
Analogue current or resistance measurement input (RMI)
(Current input: 0 to 20 mA, or 4 to 20 mA;
Pt100/1000: -40 to 250 ºC;
Resistance measurements: 0 to 2.5 kΩ;
Digital inputs (dry contact with cable supervision): maximum 330 Ω for ON detection;
Minimum current rating for connected relays: 2.5 mA)
20
21
22
COM
Common
Analogue input common
*Note: Class societies require an independent power supply for the EIM. The EIM must therefore not be connected to the same
power supply source as the PSM.
13.9.3 Frame ground characteristics
More information
See
Hardware characteristics and configuration
,
General characteristics
,
Frame ground characteristics
.
DESIGNER'S HANDBOOK 4189340911K UK
Page 446 of 521