Function
Details
[Source] > Current (I) - ACM3.2 > [Equipment] | L2 (Neutral
side) [A]
The controller outputs the L2 current from the neutral side.
[Source] > Current (I) - ACM3.2 > [Equipment] | L3 (Neutral
side) [A]
The controller outputs the L3 current from the neutral side.
[Source] > Current (I) - ACM3.2 > [Equipment] | Min (Neutral
side) [A]
The controller outputs the lowest phase current from the neutral
side.
[Source] > Current (I) - ACM3.2 > [Equipment] | Max (Neutral
side) [A]
The controller outputs the highest phase current from the neutral
side.
[Source] > Current (I) - ACM3.2 > [Equipment] | L1 differential
[A]
The controller outputs the difference between the consumer and
the neutral side of the L1 current.
[Source] > Current (I) - ACM3.2 > [Equipment] | L2 differential
[A]
The controller outputs the difference between the consumer and
the neutral side of the L2 current.
[Source] > Current (I) - ACM3.2 > [Equipment] | L3 differential
[A]
The controller outputs the difference between the consumer and
the neutral side of the L3 current.
[Source] > Current (I) - ACM3.2 > [Equipment] | Min differential
[A]
The controller outputs the lowest difference between the
consumer and the neutral side phase currents.
[Source] > Current (I) - ACM3.2 > [Equipment] | Max differential
[A]
The controller outputs the highest difference between the
consumer and the neutral side phase currents.
[Source] > Current (I) - ACM3.2 > [Equipment] | L1 restraint [A]
The controller outputs the L1 restraint current.
[Source] > Current (I) - ACM3.2 > [Equipment] | L2 restraint [A]
The controller outputs the L2 restraint current.
[Source] > Current (I) - ACM3.2 > [Equipment] | L3 restraint [A]
The controller outputs the L3 restraint current.
[Source] > Current (I) - ACM3.2 > [Equipment] | Min. restraint
[A]
The controller outputs the lowest phase restraint current.
[Source] > Current (I) - ACM3.2 > [Equipment] | Max. restraint
[A]
The controller outputs the highest phase restraint current.
[Source] > Current (I) - ACM3.2 > [Equipment] | Frequency [Hz]
The controller outputs the frequency of the phase with the
highest frequency (based on the ACM3.2 current
measurements).
Table 3.11
[Source] power analogue output functions
Function
Details
[Source] > Power (P) > [Equipment] | L1 [kW]
The controller outputs the L1 power.
[Source] > Power (P) > [Equipment] | L2 [kW]
The controller outputs the L2 power.
[Source] > Power (P) > [Equipment] | L3 [kW]
The controller outputs the L3 power.
[Source] > Power (P) > [Equipment] | Total [kW]
The controller outputs the total power.
[Source] > Power (P) > [Equipment] | Min. [kW]
The controller outputs the power of the phase with the lowest power.
[Source] > Power (P) > [Equipment] | Max. [kW]
The controller outputs the power of the phase with the highest power.
[Source] > Power (P) > [Equipment] | Total [%]
The controller outputs the total power, as a percentage of the source's
nominal power.
[Source] > Power (P) > [Equipment] | Available [kW]
The controller outputs the available power for the source in kW. Available
power = Nominal power - Total power
[Source] > Power (P) > [Equipment] | Available [%]
The controller outputs the available power for the source, as a percentage of
the source's nominal power. Available power = Nominal power - Total power
DESIGNER'S HANDBOOK 4189340911K UK
Page 57 of 521