Table 13.29
EIM3.1 terminals
Module
Count Symbol Type
Name
1
2
3
4
5
6
7
10
9
8
11
12
13
14
15
16
17
21
20
19
18
22
F/G
+
-
COM
EIM3.1
COM
COM
W
*
1
Ground
Frame ground
1
+
-
12 or 24 V DC
Power supply
3
Relay output
Configurable
1
*
Relay output (with wire break detection)
Configurable
4
Digital input
Configurable
1
MPU input (with wire break detection)*
Magnetic pickup
1
W
W input (no wire break detection)*
Generator tacho output or NPN/PNP
sensor
3
Analogue current or resistance measurement input (RMI) Configurable
*Note: These inputs cannot both be used at the same time.
Table 13.30
EIM3.1 technical specifications
Category
Specification
Frame ground
Voltage withstand: ±36 V DC to the power supply positive (terminal 1)
Voltage withstand: ±36 V DC to the power supply negative (terminal 2)
Auxiliary power supply
+
-
Input voltage: 12 or 24 V DC nominal (8 to 36 V DC continuously)
UL/cUL Listed: 10 to 32.5 V DC
0 V DC for 50 ms when coming from at least 8 V DC (cranking dropout)
Consumption: Typical 3 W, maximum 5 W
The auxiliary supply inputs are internally protected by a 12 A fuse (not replaceable) (fuse size
determined by load dump requirements).
Voltage withstand: ±36 V DC
Load dump protected by TVS diodes.
Start current
•
Power supply current limiter
◦
24 V: 0.6 A minimum
◦
12 V: 1.2 A minimum
•
Battery: No limit
Relay outputs
Relay type: Electromechanical
Electrical rating and UL/cUL Listed: 30 V DC and 6 A, resistive
Voltage withstand: ±36 V DC
Relay output with wire
break detection
Relay type: Electromechanical
Electrical rating and UL/cUL Listed: 30 V DC and 6 A, resistive
Includes wire break detection
DESIGNER'S HANDBOOK 4189340911K UK