[Counter pulse]
[Counter]
Reactive energy import pulse 1
Reactive energy import
Active energy differential pulse 1
Active energy differential
Reactive energy differential pulse 1
Reactive energy differential
Application example for an energy counter output
1. Connect the digital output to an external counter.
2. Configure the digital output using the display unit or PICUS to
Active energy export pulse 1
.
3. Configure the
Pulse every
parameter to the value where you would like to send a pulse. For example, 100 kWh.
4. Configure the
Pulse length
to the required length of the pulse for your external counter. For example, 1 second.
With the example setup the controller sends a 1 second pulse to the external counter for each 100 kWh the controller logs.
12.5 BUS TIE breaker controller protections
12.5.1 BUS TIE breaker controller alarms
INFO
These alarms are in addition to the AC protections and general alarms for PPM 300 controllers.
Alarms
Power management
Heavy consumer feedback timeout (1 alarm for each heavy consumer)
Heavy consumer reservation not possible (1 alarm for each heavy consumer)
Advanced blackout
prevention
P load sharing failure on DG (low frequency)
P load sharing failure on DG (high frequency)
Q load sharing failure on DG (low voltage)
Q load sharing failure on DG (high voltage)
Overload on a DG
Reverse power on a DG
Reactive power export on a DG
Reactive power import on a DG
Over-current on a DG
12.5.2 Alarm actions
The controller has the following alarm actions:
•
Warning
•
Block
•
PMS-controlled open breaker
•
Trip bus tie breaker
12.5.3 Inhibits
The BUS TIE breaker controller includes the following inhibits:
DESIGNER'S HANDBOOK 4189340911K UK
Page 409 of 521