Function
I/O
Type
Details
V
new
= V
nom
+ (V
nom
× Voltage offset)
Regulators > AVR > Reactive
power set point [%]
Analogue
input
% of nominal
reactive
power
When configured, the controller receives the reactive power set
point from this analogue input. The internal controller value for
the reactive power set point is ignored.
Regulators > AVR > Cos phi set
point
Analogue
input
-
When configured, the controller receives the cos phi set point
from this analogue input. The internal controller value for the
cos phi set point is ignored.
Regulators > GOV > External
set points > Activate external f
offset
Digital input
Pulse
When activated, the controller changes
Configure >
Parameters > Regulators > GOV general configuration >
External offset > Frequency offset enable
to
Enabled
.
Regulators > GOV > External
set points > Deactivate external
f offset
Digital input
Pulse
When activated, the controller changes
Configure >
Parameters > Regulators > GOV general configuration >
External offset > Frequency offset enable
to
Not enabled
.
Regulators > GOV > External
set points > Activate external P
set point
Digital input
Pulse
When activated, the controller changes
Configure >
Parameters > Regulators > GOV general configuration >
External offset > P set point enable
to
Enabled
.
Regulators > GOV > External
set points > Deactivate external
P set point
Digital input
Pulse
When activated, the controller changes
Configure >
Parameters > Regulators > GOV general configuration >
External offset > P set point enable
to
Not enabled
.
Regulators > AVR > External
set points > Activate external V
offset
Digital input
Pulse
When activated, the controller changes
Configure >
Parameters > Regulators > AVR general configuration >
External offset > Voltage offset enable
to
Enabled
.
Regulators > AVR > External
set points > Deactivate external
V offset
Digital input
Pulse
When activated, the controller changes
Configure >
Parameters > Regulators > AVR general configuration >
External offset > Voltage offset enable
to
Not enabled
.
Regulators > AVR > External
set points > Activate external Q
set point
Digital input
Pulse
When activated, the controller changes
Configure >
Parameters > Regulators > AVR general configuration >
External offset > Q set point enable
to
Enabled
.
Regulators > AVR > External
set points > Deactivate external
Q set point
Digital input
Pulse
When activated, the controller changes
Configure >
Parameters > Regulators > AVR general configuration >
External offset > Q set point enable
to
Not enabled
.
Regulators > AVR > External
set points > Activate external
cos phi set point
Digital input
Pulse
When activated, the controller changes
Configure >
Parameters > Regulators > AVR general configuration >
External offset > Cos phi set point enable
to
Enabled
.
Regulators > AVR > External
set points > Deactivate external
cos phi set point
Digital input
Pulse
When activated, the controller changes
Configure >
Parameters > Regulators > AVR general configuration >
External offset > Cos phi set point enable
to
Not enabled
.
Governor parameters
You can configure the governor common settings under
Configure > Parameters > Regulators > GOV general configuration
.
INFO
To see these parameters, you must assign a governor output function.
External offset
These parameters allow analogue inputs to determine the genset's frequency or power set point.
Parameter
Range
Default
Notes
Frequency offset
enable
•
Not enabled
•
Enabled
Not
enabled
•
Not enabled
: The controller ignores the
Frequency offset [%]
analogue
input and Modbus input.
DESIGNER'S HANDBOOK 4189340911K UK
Page 186 of 521