64
H16
H16
01:
TK1 oil circuit
error
02:
TK2 oil circuit
error
03:
TK3 oil circuit
error
04:
TK4 oil circuit
error
05:
TK5 oil circuit
error
I/F
Oil detection
circuit error
All stopped
The temperature change of TK1
cannot be detected even after
Compressor 1 starts operating.
• Check the TK1 sensor
installation.
• Check the TK1 sensor resistant
characteristics.
• Check the misconnection of TK1,
TK2, TK3, TK4, or TK5.
• Check the SV3E and SV3F valve
error.
• Check the oil circuit capillary
clogging and non-return valve
error.
• Check the hibernating refrigerant
in compressor.
The temperature change of TK2
cannot be detected even after
Compressor 2 starts operating.
• Check the TK2 sensor
installation.
• Check the TK2 sensor resistant
characteristics.
• Check the misconnection of TK1,
TK2, TK3, TK4, or TK5.
• Check the SV3E and SV3F valve
error.
• Check the oil circuit capillary
clogging and non-return valve
error.
• Check the hibernating refrigerant
in compressor.
The temperature change of TK3
cannot be detected even after
Compressor 3 starts operating.
• Check the TK3 sensor
installation.
• Check the TK3 sensor resistant
characteristics.
• Check the misconnection of TK1,
TK2, TK3, TK4, or TK5.
• Check the SV3E and SV3F valve
error.
• Check the oil circuit capillary
clogging and non-return valve
error.
• Check the hibernating refrigerant
in compressor.
The temperature change of TK4
cannot be detected even after
Compressor 4 starts operating.
• Check the TK4 sensor
installation.
• Check the TK4 sensor resistant
characteristics.
• Check the misconnection of TK1,
TK2, TK3, TK4, or TK5.
• Check the SV3E and SV3F valve
error.
• Check the oil circuit capillary
clogging and non-return valve
error.
• Check the hibernating refrigerant
in compressor.
The temperature change of TK5
cannot be detected even after
Compressor 5 starts operating, or
the temperature difference from that
of the other TK sensor changes only
in the specified range for a given
time or longer.
• Check the TK5 sensor
installation.
• Check the TK5 sensor resistant
characteristics.
• Check the misconnection of TK1,
TK2, TK3, TK4, or TK5.
• Check the SV3E and SV3F valve
error.
• Check the oil circuit capillary
clogging and non-return valve
error.
• Check the hibernating refrigerant
in compressor.
H25
H25
–
I/F
Misconnection
of outdoor
discharge
temperature
sensor (TD3)
All stopped
The discharge temperature (TD3)
does not rise while the compressor
3 is running.
• Check installation of the TD3
sensor.
• Check the connector connection
and wiring of the TD3 sensor.
• Check the TD3 sensor resistant
characteristics.
• Check the outdoor PC board (I/F)
error.
Check code
Location
of
detection
Check code
name
System status
Error detection conditions
Items to check (locations)
Local
remote
controller
7-segment display of
outdoor unit
Check
code
Sub code