166
Installation Manual
2) When switching between low / high from an external device
SW2 [Low: ON, High: OFF]
• For NRC-01HE (remote controller for the Air to Air Heat Exchanger with DX Coil Unit), the message on the
display is changed. However, when the air conditioner operates Air to Air Heat Exchanger with DX Coil
Unit system linked with air conditioners, ventilation fan speed (Low / High) is changed though the
ventilation amount is not shown on the display.
• If a command is sent to one of the units in the group, all the Air to Air Heat Exchanger with DX Coil Units
in the group operate together.
• The latter operation of the remote controller or the external device overrides the former.
(locally procured)
Adapter for remote ON/OFF control
NRB-1HE
CN705
Control circuit board of the
Air to Air Heat Exchanger
with DX Coil Unit
SW1
Low is applied when SW2
is closed, and High when
it is open.
As these terminals are not used, insulate them.
(1), (3)
No voltage
a-contact
Yellow (2)
Red (3)
White (4)
Green (1)
Black (5)
2 m