30
25
Central
control mode
switch
1) Depending on the central control device setting, the functions that can be operated
by the indoor unit remote controller can be changed.
2) Settings
*The ventilation ON / OFF operation becomes valid when the single operation of
ventilation CODE [31] of the remote control group header unit is set to "1: Possible"
in linkage to a normal indoor unit.
• "Central control"
appears (lights up) in
central control mode.
• The display blinks
when operations that
are not allowed to be
performed are to be
changed by the remote
controller.
26
Damper
output
1) Damper output setting
• The normal setting can be changed to the nighttime heat purge setting depending on
the DN setting.
• The output setting can be changed with CODE No. (DN) [5C].
2) Operation output ON / OFF conditions in the normal setting
• ON when the fan is stopped forcedly
• ON when the fan is stopped in damper switch
• ON from nighttime heat purge monitoring start to end
• OFF when the operation is stopped
3) Operation output ON / OFF conditions in the nighttime heat purge setting
The same as the normal setting except for the following:
• OFF when the nighttime heat purge operation is stopped temporarily
CODE No.
[5C]
27
Power
saving mode
1) Performed when the SAVE button on the remote controller is pressed.
2) The "SAVE" segment lights up on the wired remote controller display in saving
operation.
3) The requirement capacity ratio is limited to the following in saving operation:
4) If the power saving operation is enabled, the settings are retained when the
operation is stopped, when the mode is changed, or when the power is reset. The
power saving operation will be enabled the next time the operation starts.
The power saving
operation cannot be set
by the remote controller
of AMT31E or older.
The estimate of the
requirement capacity
ratio is 75 %.
No.
Item
Specification outline
Remarks
TCC-LINK central control
(O: Accessible
u
: Inaccessible)
Operations by
TCC-LINK
central control
On NRC-01
On
NRC-01H
ON /
OFF
setting
Ventila-
tion
ON /
OFF
Opera-
tion
switch
Timer
setting
Temper-
ature
setting
Ventila-
tion
mode
setting
Ventila-
tion
fan
speed
setting
Individual
O
O
O
O
O
O
O
"Central
control"
is
displayed
[Central 1]
u
O
O
u
O
O
O
[Central 2]
u
O
u
u
u
O
O
[Central 3]
O
O
u
O
u
O
O
[Central 4]
O
O
u
O
O
O
O
SET DATA
0
1
Damper output
Normal (default)
Nighttime heat purge
compatible
Cool / Dry
Heat
Upper limit
S8
SA