173
Installation Manual
Setting the single operation of the Air to Air Heat Exchanger with
DX Coil Unit (Setting for the header air conditioner)
Single operation of the Air to Air Heat Exchanger with DX Coil Unit is possible when operation of the Air to Air Heat
Exchanger with DX Coil Unit is linked with that of the air conditioners.
Use the
button of the wired remote controller.
* While the Air to Air Heat Exchanger with DX Coil Unit is in operation,
is displayed on the remote controller.
* Adjust this setting for the header air conditioner in the group when using a system equipped with the Air to Air
Heat Exchanger with DX Coil Unit and air conditioners.
* This setting is invalid when using a system equipped with the Air to Air Heat Exchanger with DX Coil Unit(s) only.
• Select [31] in step 3 on page 169.
• Select [0001] in step 4 on page 170.
REQUIREMENT
Do not change this setting when the operation is linked by a signal from an external device or remotely controlled on
and off (page 164) by using Remote ON/OFF Adapter NRB-1HE (sold separately).
Remote controller sensor
Usually the temperature sensor of the indoor unit senses the temperature. Configure this setting in order to sense
the temperature around the remote controller.
• Select [32] for CODE NO. in Step 3.
• Select CODE NO. from the following table in Step 4:
If the remote controller sensor blinks, an error has occurred on the remote controller sensor.
Set [0000]: Do not use for the remote controller sensor, or replace the remote controller.
Setting of the unbalanced ventilation Fan speed
SA / EA unbalanced operation of the Air to Air Heat Exchanger with DX Coil Unit is possible.
Use the
button of the remote controller.
* Adjust this setting for all the Air to Air Heat Exchanger with DX Coil Units when group operation is applied.
* Though RBC-AMT32E cannot be used, this setting can still be changed. For details, refer to “Ventilation Fan
speed setting” on page 175.
• Select [48] in step 3 on page 170.
• Select [0001: SA (High) > EA (Low) active] or [0002: SA (Low) < EA (High) active] in step 4 on page 170.
Code
SET DATA
0000
0001
31
Single operation of the fan
Invalid
(Factory default)
Valid
Code
SET DATA
0000
0001
32
Remote controller sensor
Do not use
(default)
Use
Code
SET DATA
0000
0001
0002
48
Unbalanced ventilation Fan
speed
Invalid
(Factory default)
SA (High) > EA (Low)
active
SA (Low) < EA (High)
active