60
E28
E28
Detected outdoor
unit No.
I/F
Terminal
outdoor error
All stopped
The center outdoor unit has
received an error code from the
terminal outdoor unit.
• Check the check code of the
terminal outdoor unit.
<Useful function>
If SW04 is pressed for 1 second or
longer while [E28] is displayed on
the 7-segment display of the center
outdoor unit, the fan of the outdoor
unit that has been stopped
abnormally will run.
If SW04 and SW05 are pressed
simultaneously, the fan of the
normal outdoor unit starts running.
If SW05 is pressed alone, the fan
stops.
E31
E31
ż
: IPDU error
I/F
IPDU
communication
error
All stopped
There is no more communication of
each IPDU (PC board) in the
inverter box.
• Check the connector connection
for IPDU-I/F board
communications.
• Check the outdoor PC board (I/F,
A3-IPDU, Fan IPDU) error.
• Check the external noise.
F01
–
–
Indoor
Indoor TCJ
sensor error
Only the target
unit stopped
The sensor resistance is infinite or
zero (open circuit or short circuit).
• Check the connector connection
and wiring of the TCJ sensor.
• Check the TCJ sensor resistant
characteristics.
• Check the indoor PC board error.
F02
–
–
Indoor
Indoor TC2
sensor error
Only the target
unit stopped
The sensor resistance is infinite or
zero (open circuit or short circuit).
• Check the connector connection
and wiring of the TC2 sensor.
• Check the TC2 sensor resistant
characteristics.
• Check the indoor PC board error.
F03
–
–
Indoor
Indoor TC1
sensor error
Only the target
unit stopped
The sensor resistance is infinite or
zero (open circuit or short circuit).
• Check the connector connection
and wiring of the TC1 sensor.
• Check the TC1 sensor resistant
characteristics.
• Check the indoor PC board error.
F04
F04
–
I/F
TD1 sensor
error
All stopped
The sensor resistance is infinite or
zero (open circuit or short circuit).
• Check the connector connection
of the TD1 sensor.
• Check the TD1 sensor resistant
characteristics.
• Check the outdoor PC board (I/F)
error.
F05
F05
–
I/F
TD2 sensor
error
All stopped
The sensor resistance is infinite or
zero (open circuit or short circuit).
• Check the connector connection
of the TD2 sensor.
• Check the TD2 sensor resistant
characteristics.
• Check the outdoor PC board (I/F)
error.
F06
F06
01:
TE1 sensor error
02:
TE2 sensor error
I/F
TE1, TE2
sensor error
All stopped
The sensor resistance is infinite or
zero (open circuit or short circuit).
• Check the connector connection
of the TE1, TE2 sensor.
• Check the TE1, TE2 sensor
resistant characteristics.
• Check the outdoor PC board (I/F)
error.
F07
F07
–
I/F
TL sensor error
All stopped
The sensor resistance is infinite or
zero (open circuit or short circuit).
• Check the connector connection
of the TL sensor.
• Check the TL sensor resistant
characteristics.
• Check the outdoor PC board (I/F)
error.
Check code
Location
of
detection
Check code
name
System status
Error detection conditions
Items to check (locations)
Local
remote
controller
7-segment display of
outdoor unit
Check
code
Sub code
A3-IPDU
Fan
IPDU
1
2
3
01
ż
02
ż
03
ż
ż
04
ż
05
ż
ż
06
ż
ż
07
ż
ż
ż
08
ż
09
ż
ż
0A
ż
ż
0B
ż
ż
ż
0C
ż
ż
0D
ż
ż
ż
0E
ż
ż
ż
0F
ż
ż
ż
ż