111
(Outdoor unit)
▼
Pressure sensor characteristics
• Input / Output combination table
• Output voltage – Pressure
(Indoor unit)
▼
Temperature sensor characteristics
Pin No.
High-pressure (Pd)
Low-pressure (Ps)
Input / Output name
Lead color
Input / Output name
Lead color
1
OUTPUT
White
—
—
2
—
—
OUTPUT
White
3
GND
Black
GND
Black
4
+5 V
Red
+5 V
Red
High-pressure (Pd)
Low-pressure (Ps)
0.5 to 4.3 V
0 to 3.73 MPa
0.5 to 3.5 V
0 to 0.98 MPa
Pressure (MPa)
H
igh-pressure out
put (V)
Low
-pr
essure output
(V)
Pressure (MPa)
Indoor TRA, TSA, TFA sensor
Resistance
[k
]
Temperature [°C]
Temperature [°C]
Resistance [k
]
0
33.9
5
26.1
10
20.3
15
15.9
20
12.6
25
10.0
30
8.0
35
6.4
40
5.2
45
4.2
50
3.5
55
2.8
60
2.4
Содержание MD-VNK802HEXE