15
(1) The dotted line represents a wire procured locally, and the dashed line represents an option sold separately.
(2)
represents a terminal block,
represents a connection terminal,
represents a connector on the
printed circuit board and
represents a short circuit connector.
(3)
represents a protective earth.
(4)
represents a printed circuit board.
(5) Using a no voltage a-contact input of the external input (option), the following operations are available.
Between 1 and 2 : Selecting the remote controller operation (Invalid / Valid)
Between 1 and 3 : Adjusting the fan speed (Low / High)
Between 1 and 5 : Operation (ON / OFF)
Use a microcurrent contact (DC 12 V, 1 mA). In addition, ON / OFF operation is possible when using a voltage
of DC 12 V or 24 V.
(6) Orange wire (High) is connected as factory default. To switch to “Extra High”, connect black wire's connector
instead of orange.
Code
Parts name
Code
Parts name
Code
Parts name
CN**
Connector
TFA
TFA sensor
DMV1
Decompression magnetic valve
F01
Fuse (printed circuit board)
TCJ, TC1, TC2 Indoor coil sensor
PMV
Pulse modulating valve
F02
Fuse (motor)
TB1
Terminal block (power source)
SW701
Dip switch
FM1
Air supplying motor
TB2
Terminal block (communication)
43F11, 43F12
Relay for air supplying motor
FM2
Air exhausting motor
TB3
Terminal block (external output)
43F21, 43F22
Relay for air exhausting motor
DAM
Damper motor
TB4
Terminal block (humidistat)
RY701, RY702 Relay for air supplying motor
TRA
TRA sensor
TB5
Terminal block (magnetic valve)
RY704, RY705 Relay for air exhausting motor
TOA
TOA sensor
FS1
Float switch
TSA
TSA sensor
MV1
Magnetic valve