68
P20
P20
–
I/F
High-pressure
protection
activation
All stopped
The Pd sensor detected a value
over 3.6 MPa.
• Check the Pd pressure sensor
error.
• Open and check the service
valve. (Gas, Liquid)
• Check the outdoor fan error.
• Check the outdoor fan motor
error.
• Check the outdoor PMV clogging
(PMV1, 2, 4).
• Check the heat exchanger
clogging.
• Short circuit of the outdoor
suction / discharge air
• Check the SV2 circuit clogging.
• Check the outdoor PC board (I/F)
error.
• Check indoor fan error (caused
by low air volume).
• Check the opening status of
indoor PMV.
• Check the miswiring of the
communication line between
indoor and outdoor.
• Check the check valve error in the
discharge area.
• Check the gas balance SV4 valve
circuit.
• Check the SV5 valve circuit.
• Check the refrigerant
overcharging.
P22
P22
0
: IGBT circuit
1
: Position
detection circuit
error
3
: Motor lock
error
4
: Motor current
detection
C
: TH sensor
temperature
error
D
: TH sensor
error
E
: Inverter DC
voltage error
(Outdoor fan)
Note:
0 – F appears
in "
" above.
Ignore it.
IPDU
Outdoor fan
IPDU error
All stopped
(Sub code: 0
)
FAN IPDU overcurrent protection
circuit
Overcurrent was detected when the
fan started running.
• Check the fan motor.
• Check the error of IPDU board for
fan.
All stopped
(Sub code: 1
)
FAN IPDU position detection circuit
Position detection is not performed
properly.
• Check the fan motor.
• Check the connector connection
for fan motor.
• Check the error of IPDU board for
fan.
All stopped
(Sub code: 3
)
External elements such as blowing
and obstacles
Position detection is not performed
properly.
• Check the fan motor.
• Check the error of IPDU board for
fan.
All stopped
(Sub code: 4
)
FAN IPDU overcurrent protection
circuit
Overcurrent was detected while the
fan is running.
• Check the fan motor.
• Check the connector connection
for fan motor.
• Check the error of IPDU board for
fan.
All stopped
(Sub code: C
)
The TH sensor temperature is over
a given criterion while the fan is
running.
• Check the fan motor.
• Check the error of IPDU board for
fan.
All stopped
(Sub code: D
)
The sensor resistance is infinite or
zero (open circuit or short circuit).
Check the error of IPDU board for
fan.
All stopped
(Sub code: E
)
FAN IPDU DC voltage protection
The DC voltage is over or under a
given criterion.
• Check power supply and voltage.
• Check the error of IPDU board for
fan.
• Check the connector connection
for fan motor.
P26
P26
01:
Compressor 1
02:
Compressor 2
03:
Compressor 3
IPDU
G-TR short
circuit protection
error
All stopped
Instant overcurrent was detected
when the compressor started
running.
• Check the connector connection
of the A3-IPDU board.
• Check the compressor error and
rare short circuit.
• Check the outdoor PC board (A3-
IPDU) error.
P29
P29
01:
Compressor 1
02:
Compressor 2
03:
Compressor 3
IPDU
Compressor
position
detection circuit
error
All stopped
Position detection is not performed
properly.
• Check the wiring and connector
connection.
• Check the compressor and rare
short circuit.
• Check the A3-IPDU board error.
Check code
Location
of
detection
Check code
name
System status
Error detection conditions
Items to check (locations)
Local
remote
controller
7-segment display of
outdoor unit
Check
code
Sub code