67
P10
P10
Detect indoor
addresses
Indoor
Indoor overflow
error
All stopped
• The float switch has worked.
• The float switch was broken, or
the connector was disconnected.
• Check the float switch connector.
• Check the drain pump
operations.
• Check the drain pump circuit.
• Check the drain pipe clogging.
• Check the indoor PC board error.
P13
P13
–
I/F
Outdoor
compressor
liquid
compression
error
All stopped
<Cooling>
A high pressure value was detected
in the stopped terminal unit while
the system is performing the cooling
operation.
<Heating>
The PMV 1 and 2 opening
continues being 100p or lower while
the system is performing the
heating operation and the outdoor
PMV is performing the SH control.
• Check the all-closing operations
of the outdoor PMV (1, 2, 4).
• Check the Pd and Ps sensor
error.
• Check the gas balance circuit
(SV2) clogging.
• Check the balance pipe clogging.
• Check the SV3B circuit clogging.
• Check the outdoor PC board (I/F)
error.
• Check the clogging of the oil
separator oil return circuit
capillary.
• Check the check valve leakage in
the discharge area.
P15
P15
01: TS condition
I/F
Gas leak
detection
(TS1 condition)
All stopped
Protective stop (performed when
the intake temperature is over the
judgment criterion for 10 minutes) is
repeated 4 times or more.
<TS error judgment criteria>
Cool: 60 °C or higher
Heat: 40 °C or higher
• Check the refrigerant shortage.
• Open and check the outdoor
service valve. (Gas, Liquid)
• Check the outdoor PMV clogging
(PMV1, 2).
• Check the TS1 sensor resistant
characteristics.
• Check the four-way valve error.
• Check the SV4 circuit.
02: TD condition
I/F
Gas leak
detection
(TD condition)
All stopped
Protective stop (performed when
the compressor is running in low
frequency and the discharge
temperature TD1, TD2, or TD3 is
over 108 °C for 10 minutes) is
repeated 4 times or more.
• Check the refrigerant shortage.
• Check the outdoor PMV clogging
(PMV1, 2).
• Check the TD1, TD2, or TD3
sensor resistant characteristics.
• Check the indoor filter clogging.
• Check the pipe clogging.
• Check the SV4 circuit (valve leak,
coil misinstallation).
P17
P17
–
I/F
Discharge
temperature
TD2 error
All stopped
The discharge temperature (TD2)
exceeded 115 °C.
• Open and check the outdoor
service valve. (Gas, Liquid)
• Check the outdoor PMV clogging
(PMV1, 2, 4).
• Check the TD2 sensor resistant
characteristics.
• Check the four-way valve error.
• Check the SV4 circuit leakage.
• Check the SV4 circuit.
(SV41 / SV42 / SV43 miswiring)
P18
P18
–
I/F
Discharge
temperature
TD3 error
All stopped
The discharge temperature (TD3)
exceeded 115 °C.
• Open and check the outdoor
service valve. (Gas, Liquid)
• Check the outdoor PMV clogging
(PMV1, 2, 4).
• Check the TD3 sensor resistant
characteristics.
• Check the four-way valve error.
• Check the SV4 circuit leakage.
• Check the SV4 circuit.
(SV41 / SV42 / SV43 miswiring)
P19
P19
Detected outdoor
unit No.
I/F
Four-way valve
reverse error
All stopped
A refrigerant cycling error was
detected during heating.
• Check the four-way valve error.
• Check the four-way valve coil
error and connector connection.
• Check the TS1 and TE1 sensor
resistant characteristics.
• Check the Pd, Ps pressure
sensor error output voltage
characteristics.
• Check the misconnection of the
TE1, TL sensor.
Check code
Location
of
detection
Check code
name
System status
Error detection conditions
Items to check (locations)
Local
remote
controller
7-segment display of
outdoor unit
Check
code
Sub code
Содержание MD-VNK802HEXE
Страница 120: ...118 11Owner s Manual Excerpt ...
Страница 137: ...135 12Installation Manual Excerpt ...