47
Monitoring function of wired remote controller
The following monitoring function is available if the remote controller of NRC-01HE or RBC-AMT32E is
used.
Display
<Content>
Enter the service monitoring mode using the remote
controller to check the sensor temperature or operation
status of the remote controller, indoor unit, and outdoor unit.
<Procedure>
1
Press and hold the
button for 4
seconds or longer to enter the service monitoring
mode. The service monitor lights up. The
temperature of CODE No.
appears at first.
2
Press the
button to change to CODE No. of
the item to monitor.
Refer to the following table for CODE No.
3
Press the
button to change to the item to
monitor. Monitor the sensor temperature or
operation status of the indoor unit and outdoor
unit in the refrigerant line.
4
Press the
button to return the display to normal.
*1 In the case of group connection, only the header indoor unit data can be displayed.
CODE
No.
Data
Format
Unit
Remote controller display
example
Indoo
r u
n
it
d
a
ta
00
Room temperature (in control) (*1)
x 1
°C
[0024] = 24 °C
01
Room temperature (Remote controller)
x 1
°C
02
Return Air Temperature (TRA)
x 1
°C
03
Coil Temperature (TCJ)
x 1
°C
04
Coil Temperature (TC2)
x 1
°C
05
Coil Temperature (TC1)
x 1
°C
06
Discharge temperature (TFA)
x 1
°C
08
PMV
x 1 / 10
pls
[0050] = 500 pls
F3
Filter sign time
x 1
h
[2500] = 2500 h
F9
Air Suction Temperature of direct expansion coil (TSA)
x 1
°C
[0024] = 24 °C
FA
Outdoor Air Temperature (TOA)
x 1
°C
System dat
a
0A
Number of connected indoor units
x 1
–
[0048] = 48
0B
Total horse power of connected indoor units
x 10
HP
[0415] = 41.5 HP
0C
Number of connected outdoor units
x 1
–
[0004] = 4
0D
Total horse power of outdoor units
x 10
HP
[0420] = 42 HP
Return the display
to normal.
Procedure