182
13
Exchanging and assembling the main
components
No.
Component
Procedure
Note
1
Inspection cover
1.
1.Remove the fixing cover, loosen the fixing screw,
and then remove the inspection cover.
2
Heat exchange
element
1., 2.
2.Hold the handle of the heat exchange element, and
then pull it out.
Note:
A single heat exchange element weighs 2 - 4 kg
(there are two elements). Be careful not to drop it.
3
Element rail
1. to 3.
3.Remove the two screws (M4 × 6) that fix the element
rail to pull the rail out.
4
Foam cover
1. to 4.
4.Slide the foam cover to the center of the product to
pull it out.
Fixing screw
Fixing lever
Handle of Heat exchanger
Screws (M4 × 6)
Element rail on the
left and right side
Foam cover