Codes (DN codes) for changing settings (Necessary for local advanced control)
DN
Item
Content
Factory setting
01
Filter sign lighting time
0000: None
0002: 2500 H
0004: 10000 H
0001: 150 H
0003: 5000 H
0002: 2500 H
02
Filter clogging
0000: Normal
0001: High degree of dirt
(Half of standard time)
0000: Normal
03
Central address
0001: No. 1
0099: Unfixed
–
0064: No. 64
0099: Unfixed
04
Specific indoor unit priority
0000: No priority
0001: Priority
0000: No priority
06
Heat intake temperature shift
0000: No shift
0002: +2 °C
–
0001: +1 °C
0010: +10 °C
(Recommended: Up to +6)
0002: +2 °C
0F
Cold only
0000: Heat pump
0001: Cool only
(No "AUTO" / "HEAT" display)
0000: Heat pump
10
Type code
0050: Air to Air Heat Exchanger with DX Coil Unit
0050: Air to Air Heat
Exchanger with DX Coil
Unit
11
Capacity code
0000: Unfixed
0001 - 0034
Depends on the model type
12
Line address
0001: No. 1
0099: Unfixed
–
0030: No. 30
0099: Unfixed
13
Indoor unit address
0001: No. 1
0099: Unfixed
–
0064: No. 64
0099: Unfixed
14
Group address
0000: Individual
0002: Follower unit
0001: Header unit
0099: Unfixed
0099: Unfixed
28
Auto recovery from blackout
0000: Invalid
0001: Valid
0000: Invalid
2A
Option / Abnormal input
(CN70) switch
0000: Filter input
0002: Humidifier input
0001: Alarm input
0002: Humidifier input
2E
HA terminal (T10) switch
0000: Normal (HA terminal)
0002: Fire alarm input
0001: Alarm input
(Air purifying, etc.)
0000: Normal
(HA terminal)
32
Sensor switch
0000: Body sensor
0001: Remote controller sensor 0000: Body sensor
40
Humidifier type setting
0000: No humidifier
0001: Humidifier
Depends on the type
47
Ventilation fan speed during
nighttime heat purge operation
0000: Always LOW
0001: Operate at ventilation fan
speed set last time the
operation was stopped
0000: Always LOW
48
Unbalanced fan speed
ventilation
0000: Invalid
0002: SA < EA
0001: SA > EA
0000: Invalid
4C
Nighttime heat purge setting
0000: Invalid
0001: Start in 1 hour
–
0048: Start in 48 hours
0000: Invalid
4E
Linkage with external devices
0000: ON / OFF linked
0002: OFF linked
0001: ON linked
0000: ON / OFF linked
5C
Damper output
0000: Normal
0001: Nighttime heat purge
compatible
0000: Normal
60
Timer setting
(Wired remote controller)
0000: Possible
0001: Not possible
0000: Possible
BB
Humidity judgment by outdoor
temperature
0000: Not judged
0001: Judged
0000: Not judged
BD
Continuous humidifying time
0001: 1 hour
–
0020: 20 hours
0006: 6 hours
BE
Delay after drainage
0015: 15 minutes
–
0030: 30 minutes
0015: 15 minutes
C9
Air to Air intake temperature
correction (Cool)
0000: No shift
0002: -1.0 °C
–
0001: -0.5 °C
0007: -3.5 °C
0004: -2.0 °C
CA
Air to Air intake temperature
correction (Heat)
0000: No shift
0002: 1.0 °C
–
0001: 0.5 °C
0007: 3.5 °C
0005: 2.5 °C
D0
Power saving mode
0000: Invalid
0001: Valid
0001: Valid
EA
Current ventilation mode
0002: Heat exchange mode
0003: Automatic mode
0002: Heat exchange mode
EB
Current ventilation fan speed
0002: High
0004: Unbalanced
0003: Low
0002: High
ED
Operation output
0000: Normal operation only
0002: Nighttime heat purge
only
0004: Exhausting fan linked
0001: Nighttime heat
purge
0003: Supplying fan linked
0000: Normal operation only
EE
Abnormal signal / Bypass
mode signal switch
0000: Abnormal signal output
0001: Bypass signal output
0000: Abnormal signal output