Installation Manual
Remote controller wiring
Wiring diagram
* Use a 0.5 mm
2
to 2 mm
2
wire.
Address setting
Refer to the Installation Manual of the outdoor unit for address setting.
* When the Air to Air Heat Exchanger with DX Coil Unit system linked with indoor air conditioners is used, set the
Air to Air Heat Exchanger with DX Coil Unit as “Follower”, referring to “Setting the address manually using the
remote controller” in the Installation Manual of the outdoor unit.
Switching between Extra High and High
When switching to Extra High, connect the black lead wire (Extra High) to the connector.
* The Orange lead wire (High) is connected as factory default.
* Connect the black lead wire both to the air supplying motor (white connector) and the air exhausting motor (red
connector).
* Refer to “Connection diagram” for the connection method.
Remote controller terminal block
Remote controller unit
Indoor unit remote
controller terminal
block
Remote controller wire
(locally procured)
Air exhaust
(red connector)
Air supply
(white connector)