61
F08
F08
–
I/F
TO sensor error
All stopped
The sensor resistance is infinite or
zero (open circuit or short circuit).
• Check the connector connection
of the TO sensor.
• Check the TO sensor resistant
characteristics.
• Check the outdoor PC board (I/F)
error.
F10
–
–
Indoor
Indoor TSA
sensor error
Only the target
unit stopped
The sensor resistance is infinite or
zero (open circuit or short circuit).
• Check the connector connection
and wiring of the TSA sensor.
• Check the TSA sensor resistant
characteristics.
• Check the indoor PC board error.
F11
–
–
Indoor
Indoor TFA
sensor error
Only the target
unit stopped
The sensor resistance is infinite or
zero (open circuit or short circuit).
• Check the connector connection
and wiring of the TFA sensor.
• Check the TFA sensor resistant
characteristics.
• Check the indoor PC board error.
F12
F12
–
I/F
TS1 sensor
error
All stopped
The sensor resistance is infinite or
zero (open circuit or short circuit).
• Check the connector connection
of the TS1 sensor.
• Check the TS1 sensor resistant
characteristics.
• Check the outdoor PC board (I/F)
error.
F13
F13
01:
Compressor 1
02:
Compressor 2
03:
Compressor 3
IPDU
TH sensor error
All stopped
The sensor resistance is infinite or
zero (open circuit or short circuit).
IGBT built-in temperature sensor
error
➝
Replace A3-IPDU PC board.
F15
F15
–
I/F
Miswiring of
outdoor
temperature
sensor (TE1,
TL) error
All stopped
While the compressor is running in
HEAT mode, the TE1 detection
temperature is higher than the TL
detection tempe a given
value for 3 minutes or longer.
• Check installation of the TE1 and
TL sensors.
• Check the TE1 and TL sensor
resistant characteristics.
• Check the outdoor PC board (I/F)
error.
F16
F16
–
I/F
Miswiring of
outdoor
pressure sensor
(Pd, Ps)
All stopped
The high-pressure Pd sensor and
low-pressure Ps sensor are
replaced.
The output voltage of both sensors
is 0.
• Check the connector connection
of the high-pressure Pd sensor.
• Check the connector connection
of the low-pressure Ps sensor.
• Check the pressure sensor Pd,
Ps error.
• Check the outdoor PC board (I/F)
error.
• Check the compressor
compression error.
F17
F17
–
I/F
Indoor TOA
sensor error
Only the target
unit stopped
The sensor resistance is infinite or
zero (open circuit or short circuit).
• Check the connector connection
and wiring of the TOA sensor.
• Check the TOA sensor resistant
characteristics.
• Check the indoor PC board error.
F18
F18
–
I/F
Indoor TRA
sensor error
Only the target
unit stopped
The sensor resistance is infinite or
zero (open circuit or short circuit).
• Check the connector connection
and wiring of the TRA sensor.
• Check the TRA sensor resistant
characteristics.
• Check the indoor PC board error.
F22
F22
–
I/F
TD3 sensor
error
All stopped
The sensor resistance is infinite or
zero (open circuit or short circuit).
• Check the connector connection
of the TD3 sensor.
• Check the TD3 sensor resistant
characteristics.
• Check the outdoor PC board (I/F)
error.
F23
F23
–
I/F
Ps sensor error
All stopped
The output voltage of the Ps sensor
is 0.
• Check the connector connection
of the Ps and Pd sensors.
• Check the connector connection
of the Ps sensor.
• Check the Ps sensor error.
• Check the compressor
compression error.
• Check the four-way valve error.
• Check the outdoor PC board (I/F)
error.
• Check the SV4 circuit error.
Check code
Location
of
detection
Check code
name
System status
Error detection conditions
Items to check (locations)
Local
remote
controller
7-segment display of
outdoor unit
Check
code
Sub code