manualshive.com logo in svg
background image

Model

DCM601A51
DCM601A52
DCM601A53
DCM002A51
DCM008A51
DCM009A51

User’s Manual

Содержание DCM601A51

Страница 1: ...Model DCM601A51 DCM601A52 DCM601A53 DCM002A51 DCM008A51 DCM009A51 User s Manual...

Страница 2: ...at you can refer to it whenever necessary If the equipment is transferred to a new user be sure also to hand over the manual About intelligent Touch Manager WARNING Do not modify or repair the product...

Страница 3: ...igent Touch Manager where there is a risk of moisture If moist gets into the product there is a risk of causing damage to internal electronic compo nents in addition to electric shocks Ensure that the...

Страница 4: ...erned and ventilate the room and contact your Daikin dealer Do not use the air conditioner until a qualified service person confirms that the leakage has been repaired Do not operate the air condition...

Страница 5: ...gen depletion Note that when the air conditioner is to be installed in a small room it is necessary to take proper measures so that the amount of any leaked refrigerant does not exceed the concentra t...

Страница 6: ...tlet The containers may explode because the warm airflow from the indoor or outdoor unit will affect them Do not touch the motor parts at the time of filter replacement The motor in operation is at hi...

Страница 7: ...uch as a burner is used together with the air conditioner Perform ventilation from time to time Insufficient ventilation may result in oxygen deficiency Be careful when using the air conditioner with...

Страница 8: ...erable atmospheric oil such as in cooking areas g Where there are machines generating electromagnetic radiation h Where the air contains acidic or alkaline steam or vapour Protection against snow For...

Страница 9: ...Management Points 27 2 2 Displaying Areas and Management Points 27 2 3 Starting Stopping Areas and Management Points 28 2 4 Setting up the Operation Mode for an Indoor Unit 29 2 5 Setting up the Setp...

Страница 10: ...5 1 Setting up a Schedule 67 Setting up a schedule program 68 Detailed screen and button descriptions 79 5 2 Setting up the Timer Extension 107 5 3 Setting up the Auto Changeover 109 Creating and edit...

Страница 11: ...ion Steps 147 Data Conversion 148 7 3 Outputting Function Settings 150 Operating Optional Functions 151 8 Setting up Automatic Control Functions 151 8 1 Setting up the Setback 151 8 2 Setting up the I...

Страница 12: ...up the Energy Type Setting up Energy Groups 236 Setting up the Planned Energy Consumption Setting up the Actual Energy Consumption 243 11 3 Checking the Budget to Actual Energy Consumption 247 11 4 E...

Страница 13: ...ng 290 14 1 Before Having the Product Serviced 290 14 2 Turning ON OFF the Internal Battery 301 14 3 Error Information Function 302 15 Hardware Specifications 304 15 1 iTM Hardware Specifications 304...

Страница 14: ...computers in a LAN you can set up Web Remote Management and allow a maximum of 4 managers and 16 users to simultaneously access the iTM and if a connection to the Internet is available then you can m...

Страница 15: ...3 2 1 Cautions when monitoring operating a Chiller management point A Chiller management point can read and write the specific objects on a MicroTech III controller POL687 70 MCQ which is embedded in...

Страница 16: ...management point type 5 The management points D3Chiller Inv Chiller and Chiller are treated as the Chiller management points type 6 The management points BACnet Mi and BACnet Mo are treated as the Mul...

Страница 17: ...gement point 1F North Building A 1F South Meeting Room Level 1 Level 2 Level 3 Level 4 Level 10 Management point A Aisle Management point A Management point A Aisle All Top Indoor Ventilator Indoor A...

Страница 18: ...dged items as this could damage the touch screen permanently 3 1 3 3 2 3 8 6 Standard View Icon Screen 5 4 5 7 Detailed Setup dialog The following describes how the text on each component displayed on...

Страница 19: ...appear when there are hidden lines and columns To display hidden lines and columns press or slide the scroll bars Truncated column text is displayed in a tool tip When sorting is enabled touch the he...

Страница 20: ...ting a component that is not selectable is not possible is displayed on buttons and the like when the label text is truncated due to space availability To display the label text completely touch the c...

Страница 21: ...atus When the list opens upward Open status When a row is selected 7 Text box Text box When unfocused Text box When focused Cursor Indicates the position where the next character will be entered 8 Spi...

Страница 22: ...buttons Key buttons for entering characters 2 Input area text box Displays the entered characters For the Password input dialog it displays asterisks 3 Shift key toggle button Toggles between upper a...

Страница 23: ...e maximum permitted Missing Indicates the number of characters still necessary to comply with the minimum required 6 Input switch combo box Toggles the keyboard between Special and Alph nm ltrs Specia...

Страница 24: ...set as the iTM display language a button to display the input list appears Touch the button to display a list of frequently used words and select the word to input Select a word and commit the selecti...

Страница 25: ...locale setting 3 Up Down button Increases or decreases the numeric value selected in the input area text box 2 by 1 10 1 or 10 4 AM PM setting combo box Specifies whether the time is AM or PM when ti...

Страница 26: ...ive 4 Back button Deletes one digit at a time from the last number displayed in the input area text box 5 Clear button Completely deletes the numeric value displayed in the input area text box 6 Up Do...

Страница 27: ...ntelligent Touch Manager 26 9 Input range label Displays the range of values that can be entered 10 OK button Touching this button commits the input 11 Cancel button Touching this button cancels the e...

Страница 28: ...ea and indoor unit names the operation mode setpoint and fan speed information appears For detailed operation see 4 3 Standard View List Screen 2 2 Displaying Areas and Management Points 1 2 1 Display...

Страница 29: ...Selecting Start in the On Off combo box starts the selected area or management point while selecting Stop stops the selected area or management point The icon turns green or red depending on the syst...

Страница 30: ...h you want to set up the operation mode 2 Touch the Setting button and display the Detailed Setup screen 3 Select the A C tab 4 Select the Operation Mode check box and select Fan Cool Heat Dependent A...

Страница 31: ...up the setpoint fan speed and airflow direction 2 Set up the setpoint in the Setpoint spin box and the Fan Speed using the buttons Low Middle High Automatic Available fan speed settings depend on the...

Страница 32: ...d Setup screen 5 Select the A C tab 6 Select the Airflow Direction check box and set up the Airflow Direction using the buttons Air ow direction 0 Air ow direction 1 Air ow direction 2 Air ow directio...

Страница 33: ...and display the Detailed Setup screen 3 Select the R C Prohibition tab 4 You can permit prohibit the following remote controller operations a start stop b set up the operation mode and c set up the s...

Страница 34: ...or Bypass from the combo box 5 Select the check box for Ventilation Amount and select Auto normal Low normal High normal Auto fresh up Low fresh up or High fresh up from the combo box 6 Touch the OK b...

Страница 35: ...enu List screen 2 Touch the Schedule button and display the Schedule screen 3 Select the schedule program to check 4 Touch the Confirm button on the Schedule screen and display the Confirm screen 5 Se...

Страница 36: ...creen 3 Check settings in the Area List For detailed operation see 6 1 Naming and setting up the detailed information of an area Checking settings such as Mgmt Point Name Detailed Info and Icon 1 2 3...

Страница 37: ...the Time DST Setup screen 3 On the screen the current time is displayed To change touch the Modify button 4 Enter the time in the Time Setup dialog that appears 5 Touch the OK button 6 Touch the OK b...

Страница 38: ...nd buttons to specify the date for which you want to check the history Alternatively you can display the Time Setup dialog by touching the Modify button and specify the date there 4 Enter the time in...

Страница 39: ...e cover To close the cover set it to Back Be careful not to touch the switch inadvertently 4 BACKUP Power ON OFF switch for settings backup battery Be careful not to touch the switch inadvertently 5 D...

Страница 40: ...mission occurs on the DIII NET communication line 9 MONITOR key LED Orange Green Press this switch to turn on off the monitor Doing so also causes the LED color to change as follows Off Indicates that...

Страница 41: ...Displays the list of menu items Sets up weekly and annual schedules Sets up a weekly schedule for each day Sets up schedules for special days such as extra holidays Sets up the off timer to prevent fa...

Страница 42: ...y emergency stop program Function for keeping the room temperature within a certain range Function for controlling the indoor unit s setpoint in accordance with the outdoor temperature Function for au...

Страница 43: ...tion Mgmt and Energy Navigator optional tabs The button changes to Close while the Menu List screen is being displayed 3 Standard View switch button Switches from the Layout View screen optional to th...

Страница 44: ...red into waiting for release status automatically without the icon being touched even once The balloon is not displayed if the target unit was put into waiting for release status manually by touching...

Страница 45: ...ment point 15 On Off Combo box Starts Stops the selected area or management point In the case of the system with Hydrobox 15 is only valid to operate the air conditioners To start stop the water heate...

Страница 46: ...s for which manual setup is prohibited you can only reset the filter sign Setting items of functions not available for the management point being set up do not display NOTE Common Tab Sets up items co...

Страница 47: ...abled Prohibited Disabled In the case of the system with Hydrobox choosing Stop Only or Prohibited makes the water heater to operate as Permitted NOTE 2 Operation Mode Sets up whether changing the ope...

Страница 48: ...e follows the Cool or Heat operation mode set up in the air conditioner with Changeover option To select the Dry operation mode you need to complete the initial setup Some air conditioner models do no...

Страница 49: ...iction Use this setting to limit the setpoint range that can be achieved Cooling Limit Sets up the setpoint range for the indoor unit in cooling mode Enable or disable and enter the maximum and minimu...

Страница 50: ...ation Mode Select and set up a ventilation mode from Automatic ERVentilation and Bypass This setting may not be available depending on the model NOTE 2 Ventilation Amount Select and set up a ventilati...

Страница 51: ...M to output a current voltage corresponding to the adjustment value from external equipment It is used for the adjustment of building equipment such as degree of aperture of a damper valve The range i...

Страница 52: ...g the trial You cannot set MultiState in the area NOTE HW Supply Tab Sets up the Hydrobox Change settings by selecting the relevant check boxes 1 2 3 1 On Off Reheat Sets up whether starting stopping...

Страница 53: ...ID field Displays the ID of the area or management point 3 Detailed Type field Displays the type of the area or management point 4 Port No field Displays the port number to which the management point...

Страница 54: ...s of Automatic Ctrl System Settings Operation Mgmt and Energy Navigator optional tabs 3 Standard View switch button Switches from the Layout View screen optional to the Standard View screen 4 Layout V...

Страница 55: ...s the screen to a view in which settings of areas and management points are displayed using icons 11 Information button Displays the legend for an icon or contact information for inquiries regarding t...

Страница 56: ...e indoor unit of the selected area or the selected indoor unit Low Middle High Automatic 18 Setting button Displays the Detailed Setup screen for the selected area or management point 19 Header Each t...

Страница 57: ...List switch button Switches to the Menu List screen which consists of Automatic Ctrl System Settings Operation Mgmt and Energy Navigator optional tabs 2 Standard View switch button Switches from the...

Страница 58: ...ope and drag 12 Layout selection list The title selected in this list is the displayed layout 13 Back button Displays the previous screen again 14 Information button Displays the legend for an icon or...

Страница 59: ...enabled Automatic Ctrl Tab 1 2 8 9 3 4 5 6 7 For an optional function its button is hidden unless the option is enabled NOTE 1 Schedule Allows you to set up weekly as well as annual schedules includin...

Страница 60: ...outdoor temperature to keep the difference between the outdoor and indoor temperatures within a certain range It only works in Cool mode 7 HMO Optional function This function automatically starts stop...

Страница 61: ...et up to 10 hierarchical levels 2 Mgmt Pts Changes the name detailed information and icon of management points 3 Maintenance Sets up a management point maintenance 4 Network Sets up the network IP add...

Страница 62: ...alibration Corrects the contact points of the touch panel 11 Time DST Sets up the current time and the daylight saving time 12 Regional Sets up the language to use date and time format unit of tempera...

Страница 63: ...l information etc You can also save history data to the folder on a USB memory 2 PPD Optional function This function calculates and displays the proportional distribution to each air conditioner of th...

Страница 64: ...al consumption over the planned energy consumption per year month on a graph and the like You can also compare this year s actual consumption with that of last year s 2 Equipment op Mgmt This function...

Страница 65: ...see 4 2 Standard View Icon Screen and 4 3 Standard View List Screen or the Information button 14 on the Layout View screen see 4 4 Layout View Optional Screen The Information screen consists of the Le...

Страница 66: ...e is at least one management point with communication error in the area When there is at least one management point in emergency stop in the area When all management points are in mainte nance in the...

Страница 67: ...User s Manual EM11A015B intelligent Touch Manager 66 Contact Tab 1 1 Displays contact information set up by the service person...

Страница 68: ...unit Indoor Hydrobox AHU Ventilator Ventilator Chiller D3Chiller Inv Chiller Chiller Dio D3Dio External Dio BACnet Dio Analog Ao External Ao BACnet Ao MultiState Mo BACnet Mo Area All Target manageme...

Страница 69: ...urday and Sunday Holiday 9 00 Off Every month 3rd Saturday only 9 00 to 18 00 Setpoint 28 C Cool On Creating the Weekly Schedule Create the weekly schedule Cool Office A to setpoint 28 C Monday to Fri...

Страница 70: ...ies tab to display the Input dialog for entering the program name Enter Program for Office 2 Setting up the operation start time on Monday Touch to display the Weekly Pattern tab 3 4 Select Monday usi...

Страница 71: ...70 5 Touch the Create button 5 to display the Events New program screen 6 7 Touch the Modify button 6 and display the Time input dialog to specify the operation start time Enter 9 00 AM9 00 when usin...

Страница 72: ...ts of two tabs Mgmt Point and Area Touch and display the Area tab Select Office A from the list and touch the OK button to return For the procedure for creating areas see 6 1 Setting up an Area 4 Sett...

Страница 73: ...hen the Setpoint radio button 11 Touch the Modify button Enter 28 in the Numerical Input dialog and touch the OK button to return to the A C tab Events screen Touch the OK button and return to the Eve...

Страница 74: ...n exact copy of the selected event will appear Touch the Modify button 13 and enter the operation stop time 18 00 PM6 00 when using 12 hour clock in the Time Setup dialog Touch the OK button to return...

Страница 75: ...ent set up for Monday to the other days of the week Select Monday then touch the Copy button 15 to display the Copy to Selection screen 16 Select the copy destination from the list 16 Select Tuesday W...

Страница 76: ...of the weekly schedule Cool Office A to setpoint 28 C Monday to Friday from 9 00 to 18 00 Create the weekly schedule Stop air conditioning of Office A on Saturday and Sunday In the same way as 5 Setti...

Страница 77: ...ton 18 to display the Name Input dialog Enter Working day for name and touch the OK button to rename the special day 2 Setting up the operation start stop times operation mode and setpoint Touch the E...

Страница 78: ...f the week Saturday Touch the Add button to register the special day pattern It appears in 22 To preview the calendar with the special day pattern touch the Preview button 23 Touch the Close button an...

Страница 79: ...n the Schedule Edit screen 24 Select the Enable radio button 24 and enable the Program for Office This completes the creation of the schedule program Touch the OK button to save and return to the Sche...

Страница 80: ...y a calendar 5 1 3 4 2 6 7 8 9 10 11 1 Schedule Info view area Displays registered schedule programs 2 Selected schedule view area Displays information of the program selected in the Schedule Info vie...

Страница 81: ...elected in the Schedule Info view area Touching the button displays a deletion confirmation dialog 9 Edit button Displays the Schedule Edit screen that allows you to edit the program selected in the S...

Страница 82: ...d schedule view area Displays information of the program selected in the Schedule Info view area 3 Icon button Switches the screen to Icon view 4 Information button Displays the Legend screen 5 Create...

Страница 83: ...displays a deletion confirmation dialog 9 Edit button Displays the Schedule Edit screen that allows you to edit the program selected in the Schedule Info view area 10 Calendar Copy button Displays th...

Страница 84: ...view 1 Icon Displayed information Icon of scheduled program Validity period of scheduled program Upper Left Start date Lower right End date Name Icon type Disabled Without validity period With validi...

Страница 85: ...ule Settings list Displays the list of events for the date indicated in the Date area 2 for the selected schedule program 2 Date area Displays the date and day of the week for which the events are dis...

Страница 86: ...me using 1 to 32 characters irrespective of single or double byte Duplicate names are not permitted 2 Activation radio button Enables disables the schedule program 3 Period check box combo box Selecti...

Страница 87: ...e set for the day of the week selected with the radio button will be copied 4 Delete button Deletes the schedule set to the day of the week selected with radio button Touching the button displays a de...

Страница 88: ...o Selection screen that allows you to select the destination to which the schedule set for the special day selected with the radio button will be copied 4 Delete button Deletes the schedule set to the...

Страница 89: ...ds available in the Schedule Settings view area SB Low and SB High are displayed only when the optional setback function is enabled 8 OK button Saves the edit and closes the screen 9 Cancel button Can...

Страница 90: ...aximum of 40 special day patterns in one calendar 2 button Moves up and down the order of the special day pattern selected in the Calendar Settings list 3 Delete button Deletes the special day pattern...

Страница 91: ...day pattern 8 Preview button Previews the calendar with the registered special day in the Calendar Settings list 9 OK button Saves the edit and closes the screen 10 Cancel button Cancels the edit and...

Страница 92: ...st takes precedence If two or more special days set using the Month Day setup combo box overlap the latter lower in the list takes precedence Setting up a Special Day overrides the weekly schedule set...

Страница 93: ...o select the destination of the copy 3 Preview radio button Selects the schedule to be displayed in the Calendar view area You can select the schedule program source of the copy or a schedule program...

Страница 94: ...ed in the Schedule Edit screen 3 Back button Moves the Event list view to that of the previous day of the week special day 4 Next button Moves the Event list view to that of the next day of the week s...

Страница 95: ...User s Manual EM11A015B intelligent Touch Manager 94 9 OK button Saves the edit and closes the screen 10 Cancel button Cancels the edit and closes the screen...

Страница 96: ...to copy events set up for a day of the week special day to another day of the week special day 2 3 4 1 1 Copy from text field Displays the name of day of the week special day selected in the Schedule...

Страница 97: ...96 Event Screen This screen consists of six tabs Common R C Prohibition A C Ventilator Ao Mo and HW Supply each outputting different event actions Setting items of functions not available for the mana...

Страница 98: ...he time in the Time Input dialog that appears The range of values you can enter is 00 00 to 23 59 AM00 00 to PM11 59 when using 12 hour clock 2 Mgmt Pnt Area setting area Sets up the management points...

Страница 99: ...to commit the setting Pre cool Pre heat function is a function that starts the air conditioners earlier than the time set up in the schedule to make the room temperature reach the setpoint at the set...

Страница 100: ...and the normal schedule will be executed When restarting iTM If iTM is restarted pre cool heat scheduled on the day of restart will be ignored and the normal schedule will be executed Execution of pre...

Страница 101: ...ontroller Select the setting from Permitted Stop Only and Prohibited 2 R C Operation Mode permission prohibition setting area Restricts changing the operation mode from the remote controller Select th...

Страница 102: ...on or b Setpoint shift radio button If you selected Setpoint touch the Modify button and enter the temperature in the Numerical Input dialog that appears The range of values you can enter is 30 to 70...

Страница 103: ...ving water setpoint NOTE 3 Leaving Water Setpoint Cool Sets up the outlet water temperature in cooling Touch the Modify button and enter the water temperature in the Numerical Input dialog that appear...

Страница 104: ...n the Numerical Input dialog that appears The range of values you can enter is the same as that for the Setpoint 2 but the entered values should be such that they do not invert the upper and lower lim...

Страница 105: ...et up and select the setting from the combo box 1 Ventilation Mode setting area Sets up the ventilation mode Select the setting from Automatic ERVentilation and Bypass 2 Ventilation Amount setting are...

Страница 106: ...ut a current voltage corresponding to the adjustment value from external equipment It is used for the adjustment of building equipment such as degree of aperture of a damper valve The range incrementa...

Страница 107: ...tab on the Events screen It allows you to set up the Hot water supply actions 1 Select the check box of the items to set up and select the setting using the combo box radio buttons 1 Low Noise setup...

Страница 108: ...e counted Duration will be cleared In the case of the system with Hydrobox this function cannot control the reheat start operation but only that of air conditioners NOTE 1 Touch the Timer Extension bu...

Страница 109: ...aneously set up the air conditioners may be stopped before the time set up by this function preventing the temperature to reach the setpoint at the set time Example 1 Duration is set to 30 minutes 2 P...

Страница 110: ...setpoint is changed an assessment is performed immediately and then once every 5 minutes The assessment of the control condition is performed according to the following four patterns depending on the...

Страница 111: ...is 2 C Cooling mode Heating mode Heating mode Cooling mode Heating mode Heating mode Cooling mode Representative suction temperature When Representative suction temperature Representative setpoint Hea...

Страница 112: ...tative setpoint Cool Thermal difference in 0 C 1 5 When the thermal difference is 0 C Heating mode Cooling mode Cooling mode Heating mode Heating mode Heating mode Cooling mode The following describes...

Страница 113: ...a management point that is not registered in any group based on the affiliation information displayed in 7 Selecting a management point from 6 and touching the Remove button cancels its registration...

Страница 114: ...113 Setting up the changeover conditions 9 10 1 Select a group in 9 and touch the Attributes button 10 to display the Attributes dialog box 11 12 13 2 Touching the Modify button in 11 displays the Nam...

Страница 115: ...In this mode information of the indoor unit registered at the top is used even when that indoor unit is stopped However this function does not work if the operation mode of that indoor unit is other...

Страница 116: ...button 15 To disable select Disable Cautions when Using Simultaneously with Other Control Functions 1 If the cooling setpoint is lowered by the Sliding Temperature function when this function is set u...

Страница 117: ...as intended with the settings Example When the method for referencing room temperature and setpoint is set up to Fixed and the thermal difference to 4 C 1 Heating starts with setpoint for the indoor...

Страница 118: ...intenance you can recover the iTM forcibly The following describes how to interpret the Emergency Stop view and release an emergency stop If the optional function is enabled you can divide the emergen...

Страница 119: ...ct the program to release and touch the Release button 4 Only Default is displayed for programs if the optional function is disabled When the Confirm dialog appears touch the Yes button to release the...

Страница 120: ...the Menu List screen and display the Area Setup screen see 4 5 Menu List screen System Settings Tab Fig 1 Area Management point 1F North 1F South Meeting Room Aisle Room A Room B Of ce Lighting A Buil...

Страница 121: ...ly created area is created under existing management points and areas You will not be able to create new areas in the following cases The number of areas exceeds 650 The area selected in the Area List...

Страница 122: ...touch the Delete button 4 Touching the YES button on the deletion confirmation dialog that appears deletes the selected area 1F North 1F South Aisle Of ce Lighting A Lavatory Building A Top All Indoor...

Страница 123: ...p All Indoor Ventilator Fig 5 5 1 To move an area select the area you want to move for example Meeting Room and touch the Move button 5 to display the Area Move screen The area to move and lower level...

Страница 124: ...button 1F North 1F South Aisle Lighting A Lavatory Building A Top All Indoor Ventilator Fig 6 Of ce Meeting Room Room A Room B 3 The moved area for example Meeting Room is displayed under the area sel...

Страница 125: ...e Area Member Registration screen 7 9 10 8 1 1 00 Indoor 1 1 01 1 1 02 1 1 03 1 1 04 1 1 05 Room A Fig 8 2 The list 7 displays management points and areas directly under the area being edited in the o...

Страница 126: ...10 for changing the order of members displayed in 7 at once Selecting a management point or area for example 1 1 04 to move and touching the Jump button 10 displays the Order Setup screen You can sele...

Страница 127: ...an area 12 1 Select the area to name and set up the detailed information from the Area Setup screen and touch the Attributes button 12 to display the Area Attribute Setup screen 13 14 2 Touch the Modi...

Страница 128: ...gement points and areas in the order they are listed in the Area Member Registration screen 15 16 1 Touch the Modify buttons 15 and 16 on the Area Attribute Setup screen Enter the interval for startin...

Страница 129: ...elligent Touch Manager 128 Setting up icons 17 1 Touch the Modify button 17 on the Area Attribute Setup screen to display the Icon Setup screen 2 Select an icon from the displayed icon list and touch...

Страница 130: ...save area data in CSV format Max Time 15 sc will appear Touch the Yes button to save When successfully saved the message File has been saved will appear 2 To load connect the USB memory with the CSV...

Страница 131: ...following describes how to set this up 1 Touch the Mgmt Pts button on the System Settings tab of the Menu List screen and display the Mgmt Points Setup screen see 4 5 Menu List Screen System Settings...

Страница 132: ...Same Mgmt Point name is already registered appears and it is rejected Touch the Modify button 5 for Detailed Info Enter the detailed information in the Text Input dialog that appears The maximum numbe...

Страница 133: ...ton and display the Password dialog to enter the password for unlocking the screen When administrator password and screen lock are simultaneously enabled entering the administrator password after touc...

Страница 134: ...Screen Lock select Enable in 2 To disable select Disable Selecting Enable displays the Password dialog for entering a new password Set a password using 1 to 15 alphanumeric characters The dialog will...

Страница 135: ...this function up 1 Touch the Maintenance button on the System Settings tab of the Menu List screen and display the Maintenance Settings screen see 4 5 Menu List Screen System Settings Tab 2 1 2 To se...

Страница 136: ...tor style and icon color used in the iTM unit 1 Touch the Regional button on the System Settings tab of the Menu List screen and display the Locale screen see 4 5 Menu List Screen System Settings Tab...

Страница 137: ...4 Select the temperature unit from Fahrenheit and Celsius using the Celsius Fahrenheit radio button 5 Select the decimal point CSV file separator style using the Decimal Point CSV Separation radio but...

Страница 138: ...ton and close the screen Entering an inappropriate value displays an error dialog where you will be able to enter the correct value 3 When using daylight saving time enable it in 3 and select the star...

Страница 139: ...electing Backlight Off will turn off the screen when the idle time set in step 3 elapses Touch the Preview button 2 to preview the selected screensaver Touch the screen to return to the Screensaver sc...

Страница 140: ...ettings Tab 1 2 3 2 In the Screen Luminance combo box 1 select and set the luminance level for the iTM screen to a value between 1 and 8 3 In the Buzzer combo box 2 select and set the volume for the b...

Страница 141: ...top operation from the iTM s Standard View screen Con rmation dialog 1 Touch the Confirmation Dialog button on the System Settings tab of the Menu List screen to display the Confirmation Dialog screen...

Страница 142: ...calibration screen see 4 5 Menu List Screen System Settings Tab 1 2 A cross 1 will appear 5 times on the screen Touch the center of each cross in order You can start the calibration again by touching...

Страница 143: ...pecifications CB14A005 1 Touch the Backup button on the System Settings tab of the Menu List screen see 4 5 Menu List Screen System Settings Tab 2 When the dialog that confirms the start of the backup...

Страница 144: ...d is as indicated below 1 Touch the Version Info button on the System Settings tab of the Menu List screen to display the Version Information screen see 4 5 Menu List Screen System Settings Tab 1 2 3...

Страница 145: ...ist Screen Operation Mgmt Tab A Wait dialog is displayed while the history is being acquired NOTE 1 3 4 5 6 2 2 1 displays the latest 100 history records Touch the button in 2 to display the previous...

Страница 146: ...utton 6 to display the History Output screen 7 8 7 4 Touch the Modify button 7 and display the Data Input dialog to specify the output period of the CSV file Touching the Output button 8 displays a co...

Страница 147: ...pecifications CB14A005 The following output data must be converted into the CSV format History data Energy Navigator Energy data Management point data Failure to turn off data Setpoint gap data Data o...

Страница 148: ...using the Web Remote Management function option you can save data in a compressed format zip via the Web browser on your PC Unzip the compressed files and go to step 3 Operation on PC 2 Connect the US...

Страница 149: ...the iTM on your PC 1 The folder name varies depending on the output data NOTE 2 Double click CSVOutputTool exe 1 to start the CSV output tool Data conversion starts During data conversion the CSV Out...

Страница 150: ...at in the folder The saved CSV filename varies depending on the output data The display order of the year month and day depends on the date display format selected in the locale time zone daylight sav...

Страница 151: ...ttings of programs registered with the Auto Changeover Temperature Limit Settings of groups registered with the Temperature Limit Sliding Temperature Settings of groups registered with Sliding Tempera...

Страница 152: ...or both depending on your needs Setpoint Time During absence During presence During absence Setup setpoint upper limit setpoint during absence lower limit setpoint during absence Cool setpoint during...

Страница 153: ...ive Setback Setpoint the indoor unit is stopped 2 Room temperature is continuously monitored and when it becomes lower than the Setpoint Relative Setback Setpoint the indoor unit is started again 3 Th...

Страница 154: ...unit is stopped by the Timer Extension function when setback is active NOTE The following describes how to set this up 1 Touch the Temp Setback button on the Automatic Ctrl tab of the Menu List scree...

Страница 155: ...Select the temperature for heating in the Heat Setback Recovery Temp combo box 7 The range of values you can select from is 1 to 6 C in increments of 1 C When finished touch the OK button to return t...

Страница 156: ...ng the function may also not work even if a higher value than the Relative Setback Setpoint or Relative Setup Setpoint is set Temperature Limit Since Temperature Limit is a function that works when th...

Страница 157: ...Setback Inactive Not treated as OFF Sliding Temperature HMO Setback Active Not treated as ON Setback Inactive Treated as OFF Timer Extension Start order by Setback Not treated as start trigger Stop or...

Страница 158: ...hen the status specified as the required condition continues for a specified time and outputs the specified actions to the target management points or areas The management point types and conditions t...

Страница 159: ...n as an expression 2 For the explanation of the required duration see Example Delay ON timer 15 min example on the next page Example If required duration is set to 15 minutes whether the condition has...

Страница 160: ...io D3Dio External Dio BACnet Dio Analog Ao External Ao BACnet Ao MultiState Mo BACnet Mo Area All Target management point type Operation Mode Setpoint Setpoint shift Leaving Water Setpoint Target mana...

Страница 161: ...rt The initial status of a target input management point when started is handled as unfixed Similarly to the case above the changes in status before and after unfixed are not viewed as triggers of suc...

Страница 162: ...ly show unexpected behavior Example When the program is set as follows Input 1 00 1 01 Output 1 One input status change 1 02 turns ON Output 2 All inputs status change 1 02 turns OFF Required duration...

Страница 163: ...nput is On 1 03 turns ON Required duration 0 min 1 00 Operating On Stopped Off 1 01 Operating On Stopped Off 1 02 Operating On Stopped Off 1 03 Operating On Stopped Off Interlocking control is execute...

Страница 164: ...er indoor unit a or indoor unit b goes on turn on Ventilator c The required duration is 10 minutes Output2 When both indoor unit a and indoor unit b go off turn off Ventilator c Creating the Interlock...

Страница 165: ...ection Condition combo box 4 displays a list of management points 5 for which On Off can be registered as the condition to be detected Selecting the indoor unit a and touching the Add button registers...

Страница 166: ...the Interlock Program Input screen Similarly set up the indoor unit b 9 Select the indoor unit a and touch the Timer min button 9 and enter 10 for required duration in the Numerical Input dialog that...

Страница 167: ...indoor unit a or b to be On for 10 minutes 4 Setting up the target Touch the Modify button 12 and display the Interlock Program Output Setup screen 14 15 13 13 is the list of management points and are...

Страница 168: ...select the Start radio button Touch the OK button and return to the Interlock Program Output Setup screen Touch the OK button and return to the Interlock Program Setup screen The step above finishes t...

Страница 169: ...17 and then All inputs become invalid in the Input condition combo box 18 Touch the Modify button 19 and display the Interlock Program Output Setup screen 21 22 20 Select Ventilator c from 20 and tou...

Страница 170: ...lect the On Off check box 23 select the stop radio button and touch the OK button to return to the Interlock Program Output Setup screen Likewise touch the OK button on the Interlock Program Output Se...

Страница 171: ...ff The Ventilator control program is now complete Touch the OK button and return to the main Interlocking Control screen Enabling the Interlocking Program Enable the created interlocking program 24 Se...

Страница 172: ...ist Displays registered interlocking programs 2 Activation area Enables and disables an interlocking program 3 Create button Creates a new interlocking program Touching the button displays the Name In...

Страница 173: ...s the program selected in the interlocking program list Touching the button displays the Text Input dialog 7 Edit button Displays the Interlock Program Setup screen that allows you to edit the program...

Страница 174: ...nput becomes valid All inputs become valid At least one input becomes invalid and All inputs become invalid 5 Modify button Output Displays the Interlock Program Output Setup screen that allows you to...

Страница 175: ...increments of 1 second It is 1 to 30 seconds when the Detection Condition is Analog value 3 Condition Setup button Displays the Condition Setup screen that allows you to set up the conditions require...

Страница 176: ...Points list to the Management Point Input list You can register up to 50 management points to monitor However you cannot register areas 7 Remove button Removes the management point selected in the Man...

Страница 177: ...en opens on the tab that corresponds to the type of the monitored management point Start Stop Error Tab Condition Setup Screen This screen is displayed when you touch the Start Stop Error tab on the C...

Страница 178: ...Condition Setup screen Sets up the conditions required for the operation mode to be detected 1 2 3 1 Operation Mode combo box Select the operation mode required for clearing the condition Select an o...

Страница 179: ...e inequality sign to be used in the analog value condition from and 3 Analog Value2 setting area Sets up the right side of the analog value condition a Constant Value setting area Select this area whe...

Страница 180: ...values you can enter see Appendix 2 Setup items 4 Hysteresis setting area Sets up the range of the dead zone Touch the Modify button and enter the range in the Numerical Input dialog that appears For...

Страница 181: ...e In addition you can set a hysteresis around the valid invalid border value to prevent hunting In case that the condition is set between analog values the conditions can only be set to the management...

Страница 182: ...ue Assessment Not assessed Previous assessment kept Analog value at the management point Analog value at the management point Assessment interval 1 minute Assessment interval 1 minute Failure Success...

Страница 183: ...cept above Not assessed Previous assessment kept Analog value at management point 1 Analog value at management point 1 Success Failure Hysteresis Hysteresis Assessment interval 1 minute Assessment int...

Страница 184: ...any inappropriate setting exists for example room temperature 200 C If an abnormal value is entered due to an analog sensor malfunction the analog value condition may be always cleared or not cleared...

Страница 185: ...he action to be performed by the output event selected in the Events list 4 Available Management Points Area list Displays a list of management points areas to which events can be output 5 Add button...

Страница 186: ...able for the management point being registered do not display NOTE Common Tab Action Setup Screen This screen is displayed when you touch the Common tab on the Action Setup screen Sets up actions for...

Страница 187: ...ting using the radio buttons 1 Start Stop setting area Sets up whether starting stopping the management point from the remote controller will be permitted or prohibited 2 Operation Mode setting area S...

Страница 188: ...etting area Sets up the setpoint To set up select either the a Setpoint radio button or b Setpoint shift radio button If you selected Setpoint touch the Modify button and enter the temperature in the...

Страница 189: ...Sets up the outlet water temperature in cooling Touch the Modify button and enter the water temperature in the Numerical Input dialog that appears The range of values you can enter is 30 to 70 C 4 Lea...

Страница 190: ...s to set up and select the setting from the combo box 1 Ventilation Mode setting area Sets up the ventilation mode Select the setting from Automatic ERVentilation and Bypass 2 Ventilation Amount setti...

Страница 191: ...nding to the adjustment value from external equipment It is used for the adjustment of building equipment such as degree of aperture of a damper valve The range incremental width and unit of the analo...

Страница 192: ...Tab Action Setup Screen Sets up the Hydrobox Change settings by selecting the relevant check boxes 1 2 3 1 Low Noise Enables or disables the Low Noise function 2 OK button Saves the edit and closes th...

Страница 193: ...efault program cannot be edited except from toggling enable and disable If the optional Emergency Stop function is enabled you can create your own emergency stop program The following describes how to...

Страница 194: ...name You can name the program using up to 20 characters Enter a name and touch the OK button to close the screen The program is added to the list 1 Then touch the Edit button 6 and display the Emergen...

Страница 195: ...s the air conditioners only but unable to control the water heater operation NOTE 7 Using the Release Mode combo box 13 select the method of releasing the emergency stop program from Automatic and Man...

Страница 196: ...Default program canceling the emergency stop signal input automatically releases the emergency stop Forcible release possible Programs created in this chapter can be manually released When a program i...

Страница 197: ...limit room temperature 4 C or room temperature heat setpoint sends the order to stop Assessments following an order to start cooling or heating are not performed until after a period of 30 minutes Ho...

Страница 198: ...ght 2 Create button Creates a new group and displays the Name Setup dialog that allows you to enter the name Duplicate names are not permitted You can create up to 8 Temp Limit groups Touch the OK but...

Страница 199: ...d touch the Remove button The management points you can register are limited to indoor units You can register up to 512 indoor units in one group You cannot register the same indoor unit in multiple g...

Страница 200: ...rical Input dialog In Upper Limit you can specify a temperature in the 32 C to 50 C range in increments of 1 C while in Lower Limit you can specify a temperature in the 2 C to 16 C range in increments...

Страница 201: ...started and stopped every 5 minutes hunting depending on the setpoint Example When the setpoint for Sliding Temperature calculated from the outdoor temperature is 32 C and the upper limit for this fu...

Страница 202: ...nt The outdoor temperature and setpoint are linked through the following expressions When the outdoor temperature is higher than the upper limit outdoor temperature Setpoint Upper limit setpoint When...

Страница 203: ...the right 2 Create button Creates a new group and displays the Name Setup dialog that allows you to enter the name Duplicate names are not permitted You can create up to 8 Sliding Temperature groups T...

Страница 204: ...and touch the Add button To remove a management point select one from 6 and touch the Remove button The management points you can register are limited to indoor units You can register up to 512 indoo...

Страница 205: ...where you can change the group name Touching the Modify button 9 displays the Analog Input screen where you can register the Ai management point at which the outdoor temperature will be measured 10 S...

Страница 206: ...in the 18 C to 34 C range in increments of 1 C while for lower limit outdoor temperature you can set a temperature in the 16 C to 32 C range in increments of 1 C When finished touch the OK button to...

Страница 207: ...ing to the outdoor temperature 4 If the outdoor temperature decreases the setpoint is lowered up to 20 C by this function 5 When the room temperature further decreases and becomes 16 C the Auto Change...

Страница 208: ...f suction temperature setpoint 1 C starts the indoor unit While stopped by this function if Heating Mode Optimization is changed from Enabled to Disabled in the Heating Mode Optimization Settings scre...

Страница 209: ...screen Cautions when Using Simultaneously with Other Control Functions 1 Start stop of indoor units by this function becomes the input condition for the Interlocking Control function 2 Since indoor u...

Страница 210: ...ication via E mail in the case of an error To use these functions you must set up the network on the iTM unit The following describes how to set this up 1 Touch the Network button on the System Settin...

Страница 211: ...dialog that appears For information necessary for the settings consult your network administrator 1 Controller name 2 Host name 3 IP address 4 Subnet mask 5 Default gateway address 6 Preferred DNS ad...

Страница 212: ...u change the settings in the Numerical Input dialog that appears Touch the OK button to close the screen The range of possible input port number see Appendix 1 iTM Monitoring Control Functions 4 When...

Страница 213: ...erent ranges of operations permitted in accordance with their privileges For the PC requirements to use this function see Peripheral Equipment Specifications CB14A005 LAN port Broadband Router HUB Int...

Страница 214: ...allowed to access up to 4 managers and 16 users simultaneously 1 Touch the Web Access Users button on the System Settings tab of the Menu List screen and display the Web Access Users Settings screen s...

Страница 215: ...Input dialog Enter the same password twice for confirmation Set a password using 0 to 15 alphanumeric characters Select the type of user in 7 In the case of a user set up the Managed Area and Screen M...

Страница 216: ...that can be registered Select a screen from 12 and touch the Add button to register it as the target Layout View screen You can only register one Layout View Select a registered screen from 11 and tou...

Страница 217: ...box you cannot use some special characters In the Password text box you cannot use special characters On the Layout View Screen see 4 4 Layout View Optional Screen you can monitor management points a...

Страница 218: ...r name and password in 13 and click the Login button 14 The Web Remote Management screen Icon view appears if authentication is successful 2 Entering the user name and password and clicking the User S...

Страница 219: ...nfirmation screen that appears and log off Web Remote Management Screen Logoff button The operation after login is basically the same as from the iTM unit For the operating procedure see the relevant...

Страница 220: ...User s Manual EM11A015B intelligent Touch Manager 219 Web user A has the Interlocking Control screen open Information dialog is displayed when the Web user B presses the Interlock button...

Страница 221: ...t function does not support iTM specific functions screensaver hardware setup touch panel calibration to prevent incorrect setup of the iTM unit hardware The Web Remote Management function supports th...

Страница 222: ...ver and a terminal for receiving E mails are necessary in addition to the iTM unit NOTE The following describes how to set this up Setting up the Mail Server Touch the E mail button on the System Sett...

Страница 223: ...me will be used as subject of the E mails Select the E mail resending interval in the combo box 3 You may select an interval of 1 to 72 hours in increments of 1 hour If after sending the E mail once t...

Страница 224: ...ministrator 5 URL or IP address of the SMTP Server 6 Port number of the SMTP Server 7 Authentication method for outgoing E mails Select one from No Authentication POP Before SMTP and SMTP AUTH 8 URL o...

Страница 225: ...he relevant button on the right 13 Create button Creates a new E mail address Touch the button and enter an address of up to 128 characters in the E mail Address Setup dialog that appears 14 Delete bu...

Страница 226: ...anagement point that will be target of monitoring from 17 and touch the Add button You can register up to 512 management points Selecting a management point from 16 and touching the Remove button canc...

Страница 227: ...Site Name name SMTP Server Title SMTP Server Address Address address Port number Port port Authentication Authentication method Authentication Authentication method Authentication method is one among...

Страница 228: ...User s Manual EM11A015B intelligent Touch Manager 227 Touch the OK button to send the trial e mail The screen returns to the E mail Address tab When finished touch the OK button to close the screen...

Страница 229: ...t with the 3G USB modem 1 Insert the 3G USB modem into the iTM 2 Open Menu List after the LED of the modem becomes Green blink The light of LED on the modem indicate as below Red light No radio wave G...

Страница 230: ...he controller is turned off Do not turn off the controller if calculating proportional distribution This chapter describes operations to be performed on the iTM unit The iTM is designed to measure the...

Страница 231: ...the specified counting date does not exist in the month the counting period will be automatically adjusted to match the calendar dates Excluded Time Exceptions button 2 is the button for advanced set...

Страница 232: ...for proportional distribution are not collected during excluded times This setting is normally unnecessary Set this up only when necessary and after a thorough check Excluded Time will be as indicted...

Страница 233: ...nagement function Equipment operation management function Energy administrator Test Operation For calculation of the indoor unit power Data export function Service person Trial Energy Navigator Energy...

Страница 234: ...t in the iTM implementation year and start managing the equipment operation the next year Check the actual opera tion for creating the operation plan The user performs a simple hypothesis testing on o...

Страница 235: ...ption plan for the current year Check the measured actual energy consumption Check the actual opera tion for creating the operation plan The user performs a simple hypothesis testing on operational st...

Страница 236: ...ctual visualization function Monthly energy budget actual visualization function Year to year energy comparison function Yes Yes Yes No No Yes Budget actual can be visualized by manually entering the...

Страница 237: ...up the Energy Type Setting up Energy Groups Setting up the Energy Type Set up the energy type and energy group target of the energy budget actual management Display the Energy Navigator tab of the Me...

Страница 238: ...A015B intelligent Touch Manager 237 2 Touch the Display mode button 2 and display the Display mode screen The Display mode button is available on all tabs 3 Touch the Modify button 3 and display the E...

Страница 239: ...y type You can name the energy type using up to 16 characters 6 Copy button Creates a new energy type by copying the selected energy type Enter a name in the Name Input dialog that appears Touch the O...

Страница 240: ...9 range in increments of 0 001 The unit is displayed in accordance with the energy type selected in 10 If a new energy conversion type is registered on the Energy Conversion Type Setup screen enter th...

Страница 241: ...up target of energy budget actual management 15 is the list of Energy Groups Perform the intended operation by touching the relevant button on the right 16 Create button Creates a new Energy Group You...

Страница 242: ...ou to set up the selected group 21 22 23 Set the management point from which to acquire the data to be used in energy budget actual management In an Energy Group you can only register Pi management po...

Страница 243: ...button to save the settings and return to the Energy Group screen When finished touch the Close button to return to the Display Mode screen Touch the Close button on the Display Mode screen to close t...

Страница 244: ...value 24 25 You can select a registered Energy Group using the Display item combo box 24 available on each tab of the Energy budget actual management screen Select the Energy Group to which to set th...

Страница 245: ...previous year Select the unit for the objective setting in 29 Select either a Settings by year or b Settings by month When the objective is a by year touch the Modify button 30 and enter the reductio...

Страница 246: ...In the Energy Type combo box 35 select the energy type for which to enter the actual energy consumption from Power Gas and Water You can select from the energy types included in the selected Energy Gr...

Страница 247: ...nds on the selected energy type Touch the Modify button and enter the conversion factor in the Numerical Input dialog that appears You can enter a value in the 0 to 9999 999 range in increments of 0 0...

Страница 248: ...en Energy Navigator Tab Yearly budget actual mgmt Tab Energy budget actual management Screen 1 7 4 6 2 3 5 This screen displays the yearly budget to actual energy consumption status for the Energy Gro...

Страница 249: ...anned energy consumption exist Accumulated energy consumption Planned accumulated energy consumption 0 Excess over planned energy consumption kWh Accumulated energy consumption kWh Planned yearly ener...

Страница 250: ...y consumption kWh Planned yearly energy consumption kWh Estimated energy consumption Planned accumulated energy consumption 0 Energy consumption plan achieved Nothing Estimated energy consumption kWh...

Страница 251: ...type you will be able to select the total of CO2 emitted by all types of energy Selecting the unit of energy to display in the graph from Energy CO2 and new conversion type in the Energy Unit combo bo...

Страница 252: ...kWh Caution Excess over target energy consumption Nothing kWh Estimated energy consumption kWh Target energy consumption kWh Danger Target energy consumption already exceeded Estimated energy consump...

Страница 253: ...User s Manual EM11A015B intelligent Touch Manager 252 Results may not be displayed when there are missing actual and or planned values NOTE...

Страница 254: ...it of energy to display in the graph from Energy CO2 and new conversion type in the Energy Unit combo box 17 plots the graph in 18 In the graph the horizontal axis represents each month of the year fr...

Страница 255: ...ent of the energy consumption plan Also touching a month on the graph displays the actual energy consumption for that month and the previous year s actual value in a tool tip Message Accumulated actua...

Страница 256: ...nction Yes Yes Yes No No Yes No No Engineering details Equipment operation management Trial Power Proportional Distribution Operation rules Failure to turn off sampling function Failure to turn off sa...

Страница 257: ...week Monday to Sunday No special day settings Operating hours 9 00 to 21 00 AM9 00 to PM9 00 when 12 hour clock is used Setpoint Cool 24 C Heat 24 C The following describes how to set this up and use...

Страница 258: ...r Rules button 3 and display the Operation Rule screen The Oper Rules button is available on both tabs 4 5 6 7 8 9 4 is the list of registered operation rules Perform the intended operation by touchin...

Страница 259: ...ion rule 8 Rename button Renames the selected operation rule Enter a name in the Name Input dialog that appears Touch the OK button to change the name You can name the operation rule using up to 16 ch...

Страница 260: ...the week to which you want to set up a rule Select the day of the week to edit from 10 11 is the content of operation rules 12 displays the legend Touch the Copy button 13 to copy the operation rule o...

Страница 261: ...M00 00 to PM12 00 when using 12 hour clock range and in increments of 15 minutes If the entered value is not a multiple of 15 minutes a dialog is displayed and the value rounded to a multiple of 15 mi...

Страница 262: ...can set up to 5 types of special day patterns Select the special day to edit in 19 The subsequent steps and screen interpretation are the same as for the Weekly Pattern Set up the operation rule usin...

Страница 263: ...are as follows Month Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec and Every Day 1 to 31 However non existing days cannot be selected Week 1st 2nd 3rd 4th and Last Day of the week Sunday Monday Tues...

Страница 264: ...he Calendar Copy screen 30 28 29 The name of the selected operation rule is displayed in 28 In 29 you can preview the operation rule calendar of both the source and destination of the copy Check by sw...

Страница 265: ...erature Limit Pre Cool Pre Heat are exempt from the operation rules during their operating hours 2 Automatic control functions that work when there are people in the room Auto Changeover HMO Timer Ext...

Страница 266: ...ed in the selected area are displayed The sampled information is presented in two tabs Failure to turn off tab where management points that were operating when they should be stopped are sampled and S...

Страница 267: ...izontal axis represents the number of days on which failure to turn off occurred When displayed by area the total days on which the management points included in the area were not turned off is displa...

Страница 268: ...mes Mgmt Point while in Area view Touching the button changes the view to Mgmt Point Selecting a management point from the list in Mgmt Point view and touching the Details button 8 displays the Detail...

Страница 269: ...of the Date period is displayed by default You can change the date by touching the Next and Back buttons 10 is the operational status graph The horizontal axis represents time and the vertical axis t...

Страница 270: ...s the list of dates on which deviations from the operation rule found in the selected management points The list displays the accrual dates accrual time and amount of energy consumed When finished che...

Страница 271: ...ab this screen displays the operational status for the set sampling period sampling targets and operation rules The screen interpretation and steps are the same as for the Failure to turn off tab see...

Страница 272: ...itions displayed on the current screen The data of top 50 management point area will be saved The name of the file to be output changes depending on the source tab as below Failure to turn off tab Mng...

Страница 273: ...m the Equipment operation management screen For the PC USB memory requirements to use this function see Peripheral Equipment Specifications CB14A005 The following describes the steps to output the ene...

Страница 274: ...and the last year Connect a USB memory to the iTM unit and touch the Save button In the confirmation dialog that appears touch the Yes button to start outputting data When save is complete a dialog ap...

Страница 275: ...tton 3 In the confirmation dialog that appears touch the Yes button to start outputting data When save is complete a dialog appears Touch the Close button to close the screen The data is saved in MngP...

Страница 276: ...tegrator to each iTM you can monitor operate and set up in the same way as with the iTM unit However the following are functions specific to the iTM unit and cannot be set up by accessing from the iTM...

Страница 277: ...and displays its Standard View Icon screen 3 Information button Displays the legend for the Icon view and contact information for inquiries regarding the iTM integrator 4 Menu List switch button Swit...

Страница 278: ...ew screen and access an iTM The Unlock Lock button that is usually displayed on the iTM unit is not displayed The iTM integrator can access an iTM unit even if its screen is locked 7 8 7 Controller na...

Страница 279: ...elligent Touch Manager 278 Legend Tab Information Screen This screen is displayed when you touch the Information button on the iTM integrator Standard view screen It displays the legend of icons used...

Страница 280: ...cation error When there is at least one management point connected to the iTM with error Error sign is displayed over the Operating Stop No operation When there is a system error in iTM 2 When there i...

Страница 281: ...reen This screen is displayed when you touch the Contact tab on the Information screen Displays contact information set up by the service person Contact information displayed here are contacts regardi...

Страница 282: ...egrator Standard view The setup method is the same as that of the iTM unit See 4 5 Menu List Screen Operation Mgmt Tab 1 1 History button Sets up history management of error occurrence status change c...

Страница 283: ...ervers 2 Web Access Users button Sets up Web users for Web Remote Management In iTM integrator only managers are permitted The maximum number of managers that can be registered is 4 3 Passwords button...

Страница 284: ...o be used in the iTM integrator The unit of temperature follows the locale of the accessed iTM unit NOTE 9 Backup button Exports the iTM integrator backup data to USB memory 10 Version Info button Dis...

Страница 285: ...ot simultaneously open the same setup screen History function The history displayed from the Operation Mgmt tab of the iTM integrator Menu List screen is the history of the iTM integrator unit can sav...

Страница 286: ...ata you can import export are as follows Setup export History Power proportional distribution data optional Energy Navigator data optional The output files are named in a similar way as when output by...

Страница 287: ...If a setup screen is open the settings in progress are canceled Area member registration When the OK button is pressed on the Registration screen Area attributes change When the OK button is pressed...

Страница 288: ...sed on the deletion confirmation dialog Controller name System settings changed Please access again Area member registration When the OK button is pressed on the Registration screen Area attributes ch...

Страница 289: ...ntenance 13 1 Resetting the Filter Sign Reset filter sign after cleaning the air conditioner with the sign ON 1 2 1 Select 1 with the filter sign ON on the Standard View screen and touch the Setting b...

Страница 290: ...play When the surface of the LCD of the iTM or the iTM unit is dirty wipe the dirt off with a piece of soft cloth soaked in a diluted neutral detergent and wrung sufficiently Do not use strongly acid...

Страница 291: ...cklight Auto is set to OFF Backlight Auto Off is a function that automatically turns the display OFF when the screen is left untouched for a certain period of time The display does not go out automati...

Страница 292: ...3 seconds to reflect the air conditioners current status The screen flickers each time it is refreshed but this is normal The operation performed by touching the iTM screen takes some time to be refl...

Страница 293: ...able Furthermore when there are two iTMs connected R C Prohibition and Setpoint Restriction are unavailable for the iTM set as sub Air conditioners cannot be started or stopped as the iTM went out of...

Страница 294: ...tralized monitoring screen Measure Operation commands cannot be sent to equipment in an emergency stop state Cause 3 A power failure occurred Checking method Use the iTM s Schedule function to check i...

Страница 295: ...r Change the name of the file contained in the USB memory Delete the file contained in the USB memory Confirm that deleting the file does not cause a problem The USB memory is not connected to iTM Con...

Страница 296: ...ed by schedule In the case above Interlocking Control stops 1 01 though it was started by Schedule It looks as if it is not working When setting up a schedule or interlocking control carefully conside...

Страница 297: ...r details of remote controller operation settings see 2 6 Enabling Disabling Remote Controller An area or indoor unit cannot be operated from the Standard View screen Check the Standard View screen fo...

Страница 298: ...ation of Chiller management points Cautions when monitoring setting up a Chiller A Chiller management point can read and write the specific objects on a MicroTech III controller POL687 70 MCQ which is...

Страница 299: ...embedded in an AHU via BACnet IP connection On that basis the total operation of an AHU from intelligent Touch Manager should be ensured by mechanical the installers and control engineering firms Abou...

Страница 300: ...tate because it cannot be distributed to any other air conditioner when it is set up not to distribute the power This total power needs to be separately handled as common utility expenses etc To displ...

Страница 301: ...ile is corrupt or the file is invalid due to a filename change etc Save the data again from the iTM to a USB memory and start the CSV output tool Invalid data message If the File Output Error message...

Страница 302: ...leaving the controller turned OFF for a long time 6 months or more set the BACKUP switch to OFF Setting this switch to OFF does not erase area management point settings schedules etc If power is not...

Страница 303: ...nd displaying a balloon If set up the buzzer will also sound Red Flashing System error Text System error occurred Touch this icon to check and restore Yellow Flashing Unit Limit Error Text Error occur...

Страница 304: ...The time the error occurred Name The name of the management point system where the error occurred Contents The content of the error Error Code The error code Contact an authorized dealer registered i...

Страница 305: ...1 iTM Hardware Specifications 243mm 207mm 290mm 256 6mm Power AC100 240V 50 60Hz Power consumption 23 W Emergency stop input Always a contact Contact current approximately 10 mA Size 290 243 50 W H D...

Страница 306: ...3 Copyright and Trademarks SDHC Logo is a trademark of SD 3C LLC The real time OS eT Kernel the network protocol PrCONNECT Pro the file system PrFILE2 and the USB stack PrUSB installed on this produc...

Страница 307: ...Dio management point D3Chiller management point Up to 320 Outdoor unit and Inv Chiller management point Up to 56 External management point Up to 512 Total of External management point BACnet managemen...

Страница 308: ...p to 650 Number of management points that can be used in an emergency stop signal Up to 6 Auto Changeover function Number of groups that can be created Up to 512 groups Number of management points tha...

Страница 309: ...January to December Actual energy consumption registration Conversion factor of 0 to 9999 999 can be entered Number of Energy Groups Up to 30 groups Number of Pi management points that can be registe...

Страница 310: ...to 1 From E mail addresses System functions System Settings function Passwords Administrator password 1 to 15 characters Screen unlock password 1 to 15 characters Management point area settings See Ce...

Страница 311: ...rmats Three patterns available DD MM YYYY MM DD YYYY YYYY MM DD Decimal point CSV separator or Unit of temperature Temperature symbol C F Icon color Icon color Red green Hardware Luminance 8 levels be...

Страница 312: ...ease the temperature settings by 4 C Schedule setup Interrock setup only Decrease the temperature settings by 3 C Decrease the temperature settings by 2 C Decrease the temperature settings by 1 C Incr...

Страница 313: ...Reheat Start Stop Low Noise On Off Storage Water Setpoint Celsius Example 32 C Fahrenheit Example 90 F 1 Not displayed when Setback Control is disabled 2 Not displayed when Operation Mode Dry is disab...

Страница 314: ...10 7 8 17 7 8 10 Increase the temperature settings by 3 C 7 8 10 7 8 17 7 8 10 Increase the temperature settings by 4 C 7 8 10 7 8 17 7 8 10 Fahrenheit Decrease the temperature settings by 7 F 7 8 10...

Страница 315: ...Setup for centralized monitoring Disable Interval 1 2 3 4 5 6 7 8 9 10 Analog Example 0 00 MultiState Example Cool Heat Recovery Ao Mo tab Analog Example 0 00 6 9999 99 9999 99 w o unit MultiState Ex...

Страница 316: ...e temperature settings by 1 C 7 8 7 8 13 7 8 Increase the temperature settings by 2 C 7 8 7 8 13 7 8 Increase the temperature settings by 3 C 7 8 7 8 13 7 8 Increase the temperature settings by 4 C 7...

Страница 317: ...ab Repeat Mode Enable Disable Enable Only Detailed Setup for centralized monitoring Disable Interval 1 2 3 4 5 6 7 8 9 10 Analog Example 0 00 MultiState Example Cool Heat Recovery Ao Mo tab Analog Exa...

Страница 318: ...ure Celsius Example 0 0 C 1 2 4 512 0 512 0 Step 0 1 Fahrenheit Example 32 F 1 2 4 890 954 Step 1 Generic Example 0 00 1 4 9999 99 9999 99 Step 0 01 Example Room Temp1 3 Mgmt Point Offset Temperature...

Страница 319: ...rd Screen unlock function is only available in iTM Screensaver Setup only available in iTM Hardware Setup only available in iTM Touch Panel Calibration Setup only available in iTM Time DST Setup Regio...

Страница 320: ...ed in a single line The area information identifier is described as the single byte character A while the management point information identifier is described as a single byte character P The number o...

Страница 321: ...of area configuration and CSV file format 1 2 3 8 4 5 6 7 9 10 11 12 13 1F North 1F South Meeting Room Aisle Room A Room B Indoor A Indoor B Of ce Indoor Ventilator 1 Lavatory Building A TOP ALL Indo...

Страница 322: ...ejected by SMTP server E mail Address Mail ID E mail ID E mail Error A071 SMTP user authentication failed E mail Address Mail ID E mail ID E mail Error A072 Other authentication method is required E m...

Страница 323: ...detected 3 Management Point Name Release B032 Communication restored Management Point Name Status Change Status B101 Start Stop Setback High Setback Low Management Point Name Status Source 4 Status B...

Страница 324: ...ume Energy Saving Control Energy Save Setup Source Auto Ctrl Higher level Central Control Control C101 Central Control is enabled DIII NET Control C102 Central Control is disabled DIII NET Setback Set...

Страница 325: ...sed the status change Status Source When the Status Source is Web the User Name is also added When the Status Source is other than control equipment other than iTM the Instructed by information is not...

Страница 326: ...TM Version iTM version Program Name Program name Enable Disable Program enabled disabled Enable Disable Period Validity period of the program All is output when the Schedule is enabled for all term Su...

Страница 327: ...Special day 5 Time P A Name Action Special Day Name of the Special day 1 Date or Month Day of the week setting of Special day 1 Month day Name of the Special day 2 Date or Month Day of the week settin...

Страница 328: ...uch Manager 327 A B C D Calendar Preview Week Date 1 2 3 Year Month Ditto Ditto Ditto Ditto Ditto Ditto Ditto Ditto Ditto Ditto Ditto Ditto Blank Program Name The settings of the second or subsequent...

Страница 329: ...Ditto Ditto Output 1 Detection Conditions Input condition for interlocked output Start Stop Interval sec Sequential start stop interval P A Name Action Area Mgmt Point Area Management point name Manag...

Страница 330: ...ogram enabled disabled Enable Disable Input Release Mode Release mode Automatic Manual Mgmt Point Input signal s management point name Ditto Output Specification method Output method Listed Points Unl...

Страница 331: ...ed in the group Ditto Blank Group Name Group name Enable Disable The settings of the second or subsequent program will be output following above Temperature Limit CSV file format Shadowed data are fix...

Страница 332: ...emperature Range Outdoor temperature range Upper limit Lower limit Setpoint Range Setpoint range Upper limit Lower limit Mgmt Point Name of management point included in the group Ditto Blank Group Nam...

Страница 333: ...able Enable Disable Set up excluded time Mon Ditto Ditto Tue Ditto Ditto Wed Ditto Ditto Thu Ditto Ditto Fri Ditto Ditto Sat Ditto Ditto Exceptions to Excluded Time Normal Exceptions to Excluded Time...

Страница 334: ...me Export Date Output date iTM Version iTM version Cool Recovery Temp Cool Recovery Temp Heat Recovery Temp Heat Recovery Temp High Relative Setup Setpoint Setback High Relative Setup Setpoint High Re...

Страница 335: ...Time Note 1 00 01 04 2012 0 0 0 ID Unit 512 standby power ID Unit 1 standby power 3 00 2 00 ID Unit 512 power ID Unit 1 power ID Unit 512 standby power ID Unit 512 power ID Unit 2 standby power ID Un...

Страница 336: ...low the System Settings iTM Version iTM version Data period Data period Data target Name Example All 1F Mgmt pnt Area Area Mgmt pnt Example Mgmt pnt Blank Administering Rules Name Administering Rules...

Страница 337: ...ata period Data period Data target Name Example All 1F Mgmt pnt Area Area Mgmt pnt Example Mgmt pnt Blank Administering Rules Name Administering Rules Name Month Day Special Day Pattern Jan 3rd Wed Sp...

Страница 338: ...displayed when data is of the past or there are no planned values Month Data collection start month Example 1 Data collection end month Example 12 Actual energy consumption kWh m3 Planned energy consu...

Страница 339: ...31 Actual energy consumption New Conversion Type Unit 1000 1500 Day 1 End of the month Example 31 Management point name 1 kWh m3 Displays only management point registered with an Energy Group and matc...

Страница 340: ...net Di BACnet Dio Analog Ai External Ai Internal Ai BACnet Ai Pulse Pi External Pi Internal Pi A B C D Blank Controller Name Controller name Export Date Output date The format for date and time follow...

Страница 341: ...lue 248 6 Suction Temperature Minimum Value Minimum 1 minute value in 1 hour data collection time C F 50 0 Value 120 0 58 Value 248 7 Operation time of cooling Total Accumulated indoor unit s operatio...

Страница 342: ...tion time C F 50 0 Value 120 0 58 Value 248 7 Outlet Water Temp Average 15 minute average of 1 minute data over 1 hour data collection time C F 50 0 Value 120 0 58 Value 248 8 Outlet Water Temp Maximu...

Страница 343: ......

Страница 344: ...EM11A015B 1409 HT...

Отзывы: