User’s Manual EM11A015B
intelligent Touch Manager
157
8-2
Setting up the Interlocking Control
Interlocking Control is a function that allows you to control two or more management points and/or
areas based on the status of an arbitrary management point. By using this function, you can start/
stop multiple facilities in conjunction with access/exit to/from a room or key management, or
implement free cooling.
This function monitors the change in status of the management point type specified in the input and
considers the conditions are cleared when the status specified as the required condition continues for a
specified time, and outputs the specified actions to the target management points or areas.
The management point types and conditions to detect that can be specified as input, as well as the
relationship between the conditions to detect and required conditions are as indicated in the tables below.
Management point type
Switch
Equipment
error
Analog
upper/lower
limit error
Operation
mode
Analog
value
Target
management
point
Indoor unit
Indoor
×
×
Hydrobox
×
×
×
AHU
×
×
×
Ventilator
Ventilator
×
×
×
Chiller
D3Chiller
×
×
Inv.Chiller
×
×
×
Chiller
×
×
×
Dio
D3Dio
External Dio
BACnet Dio*1
D3Di
External Di
Di
BACnet Di*1
×
×
×
Analog (Ai)
External Ai
Internal Ai
BACnet Ai*1
×
×
×
*1 BACnetDio, BACnetDi, and BACnetAi are optional.