User’s Manual EM11A015B
intelligent Touch Manager
162
Once the trigger condition is true to turn On/Off output, the iTM will not execute On/Off even if
the condition remains true. A change in the status of input must be recognized.
Example:
When the program is set as follows.
Input: 1-00, 1-01, 1-02
Output 1: One input is On
→
1-03 turns ON
Required duration: 0 min
1-00 Operating
On
Stopped
Off
1-01 Operating
On
Stopped
Off
1-02 Operating
On
Stopped
Off
1-03 Operating
On
Stopped
Off
Interlocking control is executed because
Output 1 condition is true when 1-00 is
operating.
Interlocking control is not executed
because Output 1 remains true although
1-00 and 1-01 are operating.
Interlocking control is not executed because
Output 1 remains true although 1-00, 1-01,
and 1-02 are operating.
Turned Off with remote controller