User’s Manual EM11A015B
intelligent Touch Manager
158
Condition to detect
Required condition
Required duration*2
Status
Switch
Specify the time
during which the
required condition is
continuously cleared
in the 0 to 30
minutes range, in
increments of 1
minute.
Specify which will be considered condition cleared: On or
error, or Off or normal.
* On/Off, or error/normal must be set on the management
point side.
Equipment error
Analog upper/lower
limit error
Operation mode
Specify which operation mode clears the condition.
Analog value
Specify the time
during which the
required condition is
continuously cleared
in the 1 to 30
minutes range, and
in increments of
1 minute.
Specify the analog value that clears the condition as an
expression.
*2 For the explanation of the required duration, see “Example: Delay ON timer (15 min. example)” on the
next page.
Example: If required duration is set to “15 minutes”
whether the “condition has been cleared” is assessed only after 15 minutes, and not when
the monitored target reached the specified status.
The figure below shows the example of an assessment when the required condition is
“On” and required duration, “15 minutes”.
On (Success)
Time
On/Off status
Success
Failure
Success
assessment
Required duration
cleared/not cleared
Failure
Success
15 minutes
15 minutes
15 minutes
Condition is considered not
cleared when Switch fails (Off)
Success when
simultaneously cleared
Off (Failure)
Switch
success/failure
On
Off
On
Off
Condition is not cleared because
Switch succeeded (On) but failed
(Off) before the required duration
has elapsed
Condition is considered
cleared when On status
continues for required dura-
tion