User’s Manual EM11A015B
intelligent Touch Manager
181
The following shows an example of how an analog value condition is assessed.
• The value at the management and constant value are compared as follows.
Example:
[
Analog value at the management point > Constant value ± Hysteresis
]
Analog value at the management point > Constant value
+
Hysteresis
Analog value at the management point < Constant value – Hysteresis
Success
Failure
Except above
Failure
Success
Constant
value
Hysteresis
Time
Analog value
Assessment
Not assessed (Previous assessment kept)
Analog value at the management point
Analog value at the management point
Assessment interval (1 minute)
Assessment interval (1 minute)
Failure
Success
Constant
value
Hysteresis
Assessment interval (1 minute)
Time
Analog value
Assessment
Range condition can be defined by combining the two cases above.
Example: [
Analog value at the management point
< Constant value ± Hysteresis]
Analog value at the management point
< Constant value – Hysteresis
Analog value at the management point
> Constant value + Hysteresis
Success
Failure
Except above
Not assessed (Previous assessment kept)
Analog value at the management point
Analog value at the management point