User’s Manual EM11A015B
intelligent Touch Manager
101
•
A/C Tab (Events Screen)
This screen is displayed when you touch the A/C tab on the Events screen.
It allows you to set up the air conditioner actions.
(1)
(3)
(4)
(5)
(6)
(7)
(8)
(9)
(2)
(b)
(a)
Select the check box of the items to set up and select/enter the setting using the combo box/
Modify button.
(1)
Operation Mode setting
area
Sets up the operation mode.
Select the setting from Fan, Cool, Heat, Dependent, Automatic, and Dry.
Only options applicable to the target are displayed.
(2)
Setpoint setting
area
Sets up the setpoint.
To set up, select either the
(a)
Setpoint radio button or
(b)
Setpoint shift radio button.
If you selected Setpoint, touch the Modify button and enter the temperature in the Numerical
Input dialog that appears. The range of values you can enter is –30 to 70°C, in increments of
0.1°C. (The range of temperatures set for an air conditioner is limited to the setpoint range of the
target air conditioner.)
If you selected Setpoint shift, select the amount to shift using the combo box.
Select the amount to shift the temperature from Decrease the temperature settings by 4°C,
Decrease the temperature settings by 3°C, Decrease the temperature settings by 2°C, Decrease
the temperature settings by 1°C, Increase the temperature settings by 1°C, Increase the
temperature settings by 2°C, Increase the temperature settings by 3°C, and Increase the
temperature settings by 4°C.