User’s Manual EM11A015B
intelligent Touch Manager
111
• When
Representative suction temperature – Representative setpoint (Heat) > Thermal diff 1.5
,
operation mode is changed from Heat to Cool
• When
Representative setpoint (Cool) – Representative suction temperature > Thermal diff 1.5
,
operation mode is changed from Cool to Heat
°C
Representative setpoint (Heat) +
Thermal difference in (0°C) + 1.
5
Representative
suction
temperature
3
°C
<When the thermal difference is 0°C>
Representative setpoint (Cool/Heat)
1.5°C
1.5°C
Representative setpoint (Cool) –
Thermal difference in (0°C) – 1.
5
When the thermal difference is 0°C
Heating mode Cooling mode
Cooling mode Heating mode
Heating mode
Heating mode
Cooling mode
The following describes how to create and set up an Auto Changeover group.
Creating and editing an Auto Changeover group
1. Touch the Auto Changeover button on the Automatic Ctrl. tab of the Menu List screen and
display the Automatic Changeover settings screen (see “4-5 Menu List Screen: Automatic Ctrl.
Tab”).
(1)
(2)
(3)
(4)
2.
(1)
is a list of registered Auto Changeover groups. To create a new group, touch the
Create
button
(2)
and enter the group name in the Name Setup dialog that appears. Duplicate names
are not permitted. You can create up to 512 groups.